| Plan Review Notes For Permit 03080637 |
| Permit Number |
03080637 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-27 00:00:00 | CHECKLIST: | | | 1-REVISE ANCHOR SCHEDULE FOR STORM | | | SHUTTERS. REVISE ANCHOR SPACING FOR | | | WOOD ANCHORS. SEE THE ENGINEERED | | | DRAWINGS AND REVISE AS REQUIRED. | | | **NOTE: PROVIDE COMPLETE INFORMATION | | | OR APPLY FOR A SEPARATE PERMIT. | | | 2-THERE ARE TWO DIFFERENT ENERGY CALCS | | | SUBMITTED. CLARIFY WHICH ONE IS THE | | | ONE TO BE USED. PROVIDE TWO SIGNED | | | AND SEALED ORIGINALS. CHAPTER 471 | | | FLORIDA STATUTES. | | | 3-PROVIDE ADDITIONAL ORIGINAL SOIL TEST | | | REPORT WITH ORIGINAL ENGINEER'S SEAL, | | | SIGNATURE, DATE. CHAPTER 471 FLORIDA | | | STATUTES. | | | 4-NEED RECORDED NOTICE OF COMMENCEMENT. | | | 5-PAY ADDITIONAL FEES FOR UPDATED | | | VALUATION. SEE ENCLOSED RECEIPT. |
|