| 2003-09-23 00:00:00 | *****CORRECTIONS****** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN - EXISTING AND PROPOSED, NEW |
| | TOTAL. |
| | |
| | 2.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALCS, FBC13-101.2. |
| | |
| | 3.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO |
| | THE APPLICATION.233-5025 |
| | |
| | 4.)THE WINDOW AT THE BATH IS REQUIRED |
| | TO BE SAFETY GLASS, FBC2405.2. |
| | |
| | 5.)HTS16 CONNECTOR REQUIRES 16 NAILS. |
| | HTSM16 ALSO REQUIRES TITENS; IF YOU ARE |
| | GOING TO SPECIFY FASTENERS SPECIFY |
| | ALL FASTENERS.REFER TO SIMPSON |
| | 2003 CATALOG. |
| | |
| | 6.)FEES DUE (RADON, VALUE ADJUSTMENT). |
| | $135.98, SEE ATTACHED BZ231203. |
| | |
| | 7.)THE FLOOR PLAN DOES NOT MATCH THE |
| | SITE PLAN.THE ADDITION IS SHOWN AS 23' |
| | AND LINING UP WITH THE EX. HOUSE.IF IT |
| | HAS A DIFFERENT SETBACK, IT SHOULD |
| | EITHER BE SMALLER THAN THE EX. HOUSE OR |
| | OFFSET ON THE OPPOSITE SIDE.REVISE THE |
| | FOUNDATION PLAN (ON SHEET 2, LABELED |
| | AS FLOOR PLAN) AND FLOOR PLAN, SHEET 1. |
| | |
| | 8.)IMPACT PROTECTION REQUIRED |
| | FBC1606.1.4. |
| | |
| | 9.)PROVIDE WIND DESIGN INFORMATION ON |
| | THE PLAN, FBC1606.1.7. |
| | |
| | 10.) FIRESTOP REQUIRED, FBC705.3. |
| | |
| | 11.) ATTIC ACCESS REQUIRED FBC2309.6. |
| | |
| | 12.) PROVIDE TWO COPIES OF ALL PRODUCT |
| | APPROVALS. |
| | DOOR |
| | WINDOW |
| | IMPACT PROTECTION (SHUTTERS) |
| | |
| | 13.) A DOUBLE DOOR W/SIDELITE PRODUCT |
| | APPROVAL WAS SUBMITTED.THE PLAN SHOWS |
| | A SINGLE DOOR. |
| | |
| | 14.) MULLION PRODUCT APPROVALS WERE |
| | SUBMITTED.NO MULLIONS ARE SHOWN ON |
| | THE PLANS. |