| Plan Review Notes For Permit 03080601 |
| Permit Number |
03080601 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS. | | | | | | A) THE FOLLOWING INFORMATION REQUIRED AT | | | TIME OF PERMIT APPLICATION: | | | 1. TYPE OF GAS, (LP OR NATURAL) | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. | | | 3. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 4) NOTE ON PLANS STATES ALL PIPE UNDER | | | OR IN CONCRETE SLAB TO BE PLACED IN PVC | | | SLEEVE. THIS IS NOT APPROVED. PIPING | | | SHALL NOT BE INSTALLED IN SOLID FLOOR | | | SLABS, SUCH AS CONCRETE OR MASONRY, EX- | | | CEPT WHERE THE CODE OFFICIAL DETERMINES | | | THAT THERE IS NO OTHER PRACTICAL MANNER | | | OF INSTALLING SUCH PIPING. FOR THIS TYPE | | | OFFLOOR CONSTRUCTION, THE HOUSE PIPING | | | SHALL BE INSTALLED ABOVE THE FLOOR, IN | | | AN OPEN OR FURRED SPACE, HOLLOW PARTIT- | | | ION, HOLLOW WALL, ATTIC SPACE OR PIPE | | | CHASE. SECTION 404.6 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|