2003-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS.
  
 A) THE FOLLOWING INFORMATION REQUIRED AT
 TIME OF PERMIT APPLICATION:
 1. TYPE OF GAS, (LP OR NATURAL)
 2. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4) NOTE ON PLANS STATES ALL PIPE UNDER
 OR IN CONCRETE SLAB TO BE PLACED IN PVC
 SLEEVE. THIS IS NOT APPROVED. PIPING
 SHALL NOT BE INSTALLED IN SOLID FLOOR
 SLABS, SUCH AS CONCRETE OR MASONRY, EX-
 CEPT WHERE THE CODE OFFICIAL DETERMINES
 THAT THERE IS NO OTHER PRACTICAL MANNER
 OF INSTALLING SUCH PIPING. FOR THIS TYPE
 OFFLOOR CONSTRUCTION, THE HOUSE PIPING
 SHALL BE INSTALLED ABOVE THE FLOOR, IN
 AN OPEN OR FURRED SPACE, HOLLOW PARTIT-
 ION, HOLLOW WALL, ATTIC SPACE OR PIPE
 CHASE. SECTION 404.6
  