| Plan Review Notes For Permit 03080509 |
| Permit Number |
03080509 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-20 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE SURVEY THAT IS PREPARED FOR | | | CONSTRUCTION. SURVEYORS NOTES NOTE #4 | | | DOESN'T ALLOW SURVEY SUBMITTED TO BE | | | USED FOR CONSTRUCTION. | | | 2-SPECIFY SIZES OF FASTENERS ON AIR | | | HANDLING UNIT. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | 3-PROVIDE SITE SPECIFIC ENGINEERING FOR | | | ENTRY DOOR UNDR A SEPARATE PERMIT. | | | 4-SOIL TEST REPORT: A)REVISE PROJECT | | | DESCRIPTION. PROPOSED HOUSE IS A TWO | | | STORY BUILDING, NOT ONE STORY. | | | B)NEEDS ENGINEER ORIGINAL SIGNATURE. NOT | | | RUBBER STAMP. CHAPTER 471 FL STATUTES. | | | 4-PROVIDE SPECIFIC FIREPLACE UL LISTING | | | TO VERIFY IF IS CURRENT. SBCCI REPORT | | | # 9626 WAS DELETED FROM THE LISTING. | | | 5-REVISE ROOF LOADING TABLE ON SHEET A5. | | | BOTTOM CHORD NEED TO HAVE 10# LIVE | | | LOAD. SEE TABLE 1604.1 FBC 2001.REVISE | | | THIS INFO. TO ENSURE TRUSSES ARE | | | DESIGNED INCLUDING THIS LOADING. |
|