| 2003-08-21 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | |
| | 1} THE METER IS NOT RATED FOR 400 AMPS. |
| | |
| | 2} THE SERVICE CONDUCTORS ARE NOT RATED |
| | FOR 200 AMPS.SEE 310.15(B)(6). |
| | |
| | 3} THE GROUNDING ELECTRODE CONDUCTOR IS |
| | NOT IN COMPLIANCE WITH 250.66,1/0 MIN. |
| | |
| | 4} PANEL "A" IS SHOWN AS 200 AMPS ON |
| | THJE RISER AND 150 AMPS ON THE |
| | SCHEDULE,PLEASE CORRELATE. |
| | |
| | 5} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE PER212.12 |
| | |
| | 6} PLEASE SHOW THE LOCATION OF THE |
| | DISCONNECTS,SHOWN ON THE RISER,ON THE |
| | PLAN. |
| | |
| | 7} THE GARAGE RECEPTACLES MUST COMPLY |
| | WITH 210.8.(A)(2). |
| | |
| | 8} NOTE THAT ALL KITCHEN COUNTERTOP |
| | RECEPTACLES MUST COMPLY WITH |
| | 210.8(A)(6). |
| | |
| | 9} PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5. |
| | |
| | 10} PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52.SEE |
| | REVIEWED SET. |
| | |
| | 11} THE POWDER ROOM REQUIRES AN OUTLET |
| | TO COMPLY WITH 210.52(D). |
| | |
| | 12} PLEASE SEE THAT THE PLACEMENT OF |
| | THESMOKE DETECTORS COMPLY WITH THE |
| | INTENT |
| | OF 8-1.4.1.6 NFPA-72(1999). |
| | |
| | 13} PLEASE NOTE THAT ALL PLANS |
| | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| | ING A TITLE BLOCK, MUST BE SIGNED, |
| | DATEDAND SEALED BY THE ARCH/ENGINEER OF |
| | RECORD. PER FS/FAC 481.221 & 471.025 |
| | |
| | AFTER CORRECTIONS TO COMMENTS ARE MADE, |
| | PLEASE RESUBMIT FOR REVIEW AND PROVIDE |
| | THE OLD SHEETS TO FACILITATE THE REVIEW. |
| | |
| | IF THERE AREANY QUESTIONS PLEASE CALL. |
| | |