Plan Review Notes
Plan Review Notes For Permit 03080444
Permit Number 03080444
Review Stop P
Sequence Number 1
Notes
Date Text
2003-09-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) SHT A-1 FOOD SERVICE APPROVAL COMMENT
 #3, SPECIFICATION WORKSHEETS SHALL BE
 ATTACHED TO EACH SET OF PLANS SUBMITTED
 FOR REVIEW. SEC 104.2.1
 2) SHT A-1 FOOD SERVICE EQUIPMENT SCHED.
 #7 INDICATES "OPEN", BUT FLOOR PLAN
 SHOWS A RANGE. PLEASE CLAIRFY.
 3) SHT A-1 FOOD SERVICE EQUIPMENT SCHED.
 #29, GREASE INTECEPTOR NOT APPROVED IN
 FOOD PREP. COOKING AREA. CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE FOR THE
 SIZE OF THE GREASE INTECEPTOR. WASTE
 ORDINANCE 2938-96. (561) 837-4074. ALT.
 CONTACT PERSON - MARIA ORTIZ (561) 837-
 4061.
 4) SHT M1 PLUMBING NOTES #1, ADOPTED
 CODE IS FBC-2001 PLUMBING. REVISE NOTES.
 5) SHT M1 GAS LOAD CALCULATIONS. ADOPTED
 CODE IS FBC-2001 FUEL GAS. REVISE NOTES.
 6) SHT M1 FLOOR PLAN/GREASE RISER, MOP
 SINK SHALL CONNECT TO GREASE SYSTEM.
 7) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.3.1.1
 8) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 9) THE FOLLOWING COMMENTS ARE INFORMAT-
 ION FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 10) INFORMATIONAL: THE SHUT OFF VALVE &
 UNION "DOWNSTREAM OF SOLENOID VALVE ARE
 NOT REQUIRED.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]