| 2003-09-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 AMENDMENTS, CHAPTER |
| | ONE, ADMIN. CODE |
| | |
| | 1) SHT A-1 FOOD SERVICE APPROVAL COMMENT |
| | #3, SPECIFICATION WORKSHEETS SHALL BE |
| | ATTACHED TO EACH SET OF PLANS SUBMITTED |
| | FOR REVIEW. SEC 104.2.1 |
| | 2) SHT A-1 FOOD SERVICE EQUIPMENT SCHED. |
| | #7 INDICATES "OPEN", BUT FLOOR PLAN |
| | SHOWS A RANGE. PLEASE CLAIRFY. |
| | 3) SHT A-1 FOOD SERVICE EQUIPMENT SCHED. |
| | #29, GREASE INTECEPTOR NOT APPROVED IN |
| | FOOD PREP. COOKING AREA. CONTACT RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE FOR THE |
| | SIZE OF THE GREASE INTECEPTOR. WASTE |
| | ORDINANCE 2938-96. (561) 837-4074. ALT. |
| | CONTACT PERSON - MARIA ORTIZ (561) 837- |
| | 4061. |
| | 4) SHT M1 PLUMBING NOTES #1, ADOPTED |
| | CODE IS FBC-2001 PLUMBING. REVISE NOTES. |
| | 5) SHT M1 GAS LOAD CALCULATIONS. ADOPTED |
| | CODE IS FBC-2001 FUEL GAS. REVISE NOTES. |
| | 6) SHT M1 FLOOR PLAN/GREASE RISER, MOP |
| | SINK SHALL CONNECT TO GREASE SYSTEM. |
| | 7) SUBMIT A WATER RISER DIAGRAM. SECTION |
| | 104.3.1.1 |
| | 8) RPZ BACKFLOW REQUIRED ON WATER SERV- |
| | ICE. |
| | 9) THE FOLLOWING COMMENTS ARE INFORMAT- |
| | ION FOR GAS PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | G. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | H. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 10) INFORMATIONAL: THE SHUT OFF VALVE & |
| | UNION "DOWNSTREAM OF SOLENOID VALVE ARE |
| | NOT REQUIRED. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |