Plan Review Notes
Plan Review Notes For Permit 03080444
Permit Number 03080444
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-08-27 00:00:001) PANIC BAR NOT REQUIRED ON REAR DOOR.
 IF SO DESIRED, THUMB-LATCH CANNOT
 BE INSTALLED WHEN PANIC HARDWARE IS
 PROVIDED.
  
 2) M-1 PLANS REFERENCE TO "EXISTING
 GAS TANKS. PLEASE PROVIDE MORE DETAILS
 WITH REGARDS TO SIZES, PROTECTION,
 AND ANY RELATIONSHIP TO ANY DOORS AND
 WINDOWS. COOKING EQUIPMENT HAS TO BE
 CHANGED TO ACCOMMODATE LPG INSTEAD
 OF NATURAL GAS.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY NEW HOOD, DUCT, AND FIRE
 SUPPRESSION SYSTEM.
  
 4) DUCT SMOKE DETECTOR REQUIRED ON
 RTU'S 2000 CFM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910