| Plan Review Notes For Permit 03080444 |
| Permit Number |
03080444 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-27 00:00:00 | 1) PANIC BAR NOT REQUIRED ON REAR DOOR. | | | IF SO DESIRED, THUMB-LATCH CANNOT | | | BE INSTALLED WHEN PANIC HARDWARE IS | | | PROVIDED. | | | | | | 2) M-1 PLANS REFERENCE TO "EXISTING | | | GAS TANKS. PLEASE PROVIDE MORE DETAILS | | | WITH REGARDS TO SIZES, PROTECTION, | | | AND ANY RELATIONSHIP TO ANY DOORS AND | | | WINDOWS. COOKING EQUIPMENT HAS TO BE | | | CHANGED TO ACCOMMODATE LPG INSTEAD | | | OF NATURAL GAS. | | | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY NEW HOOD, DUCT, AND FIRE | | | SUPPRESSION SYSTEM. | | | | | | 4) DUCT SMOKE DETECTOR REQUIRED ON | | | RTU'S 2000 CFM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|