Plan Review Notes
Plan Review Notes For Permit 03080444
Permit Number 03080444
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-14 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF THE
 FAC 61G1-16.004 FOR ALL INFORMATION
 REQ'D ON TITLE BLOCK FOR ARCH'S.
  
 2)NOTE: PLEASE CLARIFY AND SHOW NEW OR
 EXIST, "SHOW WINDOW" RECEPTS REQ'D BY
 210.62.
  
 3)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT, PER 600.5
  
 4)NOTE: PLEASE SEE 110.26 FOR CLEARENCE
 REQ'MENTS INFRONT OF PANEL.
  
 5)NOTE: PLEASE CLARIFY LOAD FOR TRACK LT
 -S PER 220.12B
  
 6)NOTE: PLEASE PROVIDE AIC RATING FOR
 NEW PANEL. 110.9
  
 7)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING FROM MAIN AND PANEL.
 250.110, SIZE ANY EQUIPMENT GRND PER
 250.122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]