| Date |
Text |
| 2003-08-14 00:00:00 | **************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF THE | | | FAC 61G1-16.004 FOR ALL INFORMATION | | | REQ'D ON TITLE BLOCK FOR ARCH'S. | | | | | | 2)NOTE: PLEASE CLARIFY AND SHOW NEW OR | | | EXIST, "SHOW WINDOW" RECEPTS REQ'D BY | | | 210.62. | | | | | | 3)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SIGN CIRCUIT, PER 600.5 | | | | | | 4)NOTE: PLEASE SEE 110.26 FOR CLEARENCE | | | REQ'MENTS INFRONT OF PANEL. | | | | | | 5)NOTE: PLEASE CLARIFY LOAD FOR TRACK LT | | | -S PER 220.12B | | | | | | 6)NOTE: PLEASE PROVIDE AIC RATING FOR | | | NEW PANEL. 110.9 | | | | | | 7)NOTE: PLEASE CLARIFY MEANS OF EQUIP- | | | -MENT GROUNDING FROM MAIN AND PANEL. | | | 250.110, SIZE ANY EQUIPMENT GRND PER | | | 250.122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|