| Plan Review Notes For Permit 03080442 |
| Permit Number |
03080442 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-06 00:00:00 | *****CORRECTIONS***** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)MP24 CANNOT BE USED IN A STRUCTURAL | | | APPLICATION.SEE SIMPSON CATALOG. | | | (WALL SECTION) | | | | | | 2.)PROVIDE CALCULATIONS TO SHOW DESIGN | | | UPLIFT FOR THE ROOF FRAMING (H2.5). | | | | | | 3.)HOW WILL THE STUDS ATTACH TO THE | | | SILL PLATE?SPECIFY SPACING. | | | | | | 4.)SHOW HOW THE GABLE ENDS WILL BE | | | STRUCTURALLY CONTINUOUS. |
|