Plan Review Notes
Plan Review Notes For Permit 03080423
Permit Number 03080423
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03080423
 ADD: 410 OLIVE DRIVE
 CONT:
 TEL: (954)650-0024
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 3305.5 SEPERATION, A FENCE OR SOLID
 CONSTRUCTION AT LEAST 8 FT HIGH SHALL BE
 PROVIDED ON THE BUILDING SIDE OF THE
 WALKWAY.
  
 2) 1803.2.1 HOW ARE YOU GOING TO RETAIN
 SOILS FROM THE RIGHT OF WAY FROM CAVING
 IN? THE ELEVATION ON THE WEST SIDE IS
 APPROX. 11.5', THE BOTTOM OF FOOTER"C"
 IS AT 3.75'? A DIFFERENCE OF 7.75'.
 THE BUILDING LINE IS ADJACENT TO THE
 PROPERTY LINE ON THE EAST, SOUTH & WEST
 SIDES OF THE PROPERTY,THE REPORT SUBMITT
 ED FROM ARDAMAN UNDER 7.1 SITE PREPARA-
 TION RECOMMENDATIONS, INDICATE THAT
 SHEET PILING MAY BE REQUIRED FOR THE
 (3) SIDES. THE CITY WILL REQUIRE THE
 SHEET PILING ON THE EAST, SOUTH & WEST
 SIDES. THE CITY WILL ALSO REQUIRE A SEAL
 ED COPY OF THE CANTILEVER SHEETPILE WALL
 ANALYSES, THERE WILL BE AT MOST A 2.25'
 TOE THAT THE CANTILEVERED SHEET PILE
 WILL BE WORKING WITH.THE SECOND ISSUE
 WILL BE THE VIBROFLOTATIONTAKING PLACE
 AT THE 3.75' ELEVATION LEVEL, THE CITY
 NEEDS INSURANCE THAT THE VIBROFLOTATION
 ADJACENT TO THE SHEET PILING WILL NOT EF
 FECT THE PERMITER WALL, NO INWARD MOVE-
 MENT OF THE SHEET PILING NOR DAMAGE TO
 THE ADJACENT SIDEWALKS, ROADWAY OR
 INTRASTRUCTURE.
  
 4) PLEASE EXPLAIN YOUR PROCESS FOR
 DEWATERING, WELL POINT SYSTEM, WILL THIS
 BE ON THE INTERIOR SIDE OF THE SHEET
 PILING OR THE CITY SIDE? SEE7.1.3.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026