2004-08-17 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE ORIG PLANS HAVE NOW
 BEEN VOIDED DUE TO CHANGES MADE TO PLANS
 WITH WHITE-OUT AND PEN. PLANS ARE SIGNED
 AND SEALED BY AN ENGINEER.
 PLEASE HAVE THESE PLANS RE-DONE BY THE
 ENGINEER OF RECORD AS REQUIRED UNDER
 FS 471/471.025
 PLEASE SEE NEW ELECTRICAL SHEET SUBMIT-
 -TED MUST ALSO BE DONE BY THE ENGINEER
 OF RECORD.
  
 2)NOTE: PLEASE SEE NEW REVISED SHEET
 NOW SHOWS A NEW SUB PANEL.
 PLEASE INCLUDE REVISED RISER DIAGRM FOR
 NEW EQUIPMENT.
 PLEASE ALSO INCLUDE PANEL SCHEDULES FOR
 THIS TO SHOW MIN REQUIRED CIRCUITS PER
 2002 NEC.
 PLEASEALSO INCLUDE LOAD CALC FOR NEW
 A/C,SPA TUB,GEN LTS AND RECEPTS.
 215.5/ 220.31B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  