| Plan Review Notes For Permit 03080399 |
| Permit Number |
03080399 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2004-08-17 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE ORIG PLANS HAVE NOW | | | BEEN VOIDED DUE TO CHANGES MADE TO PLANS | | | WITH WHITE-OUT AND PEN. PLANS ARE SIGNED | | | AND SEALED BY AN ENGINEER. | | | PLEASE HAVE THESE PLANS RE-DONE BY THE | | | ENGINEER OF RECORD AS REQUIRED UNDER | | | FS 471/471.025 | | | PLEASE SEE NEW ELECTRICAL SHEET SUBMIT- | | | -TED MUST ALSO BE DONE BY THE ENGINEER | | | OF RECORD. | | | | | | 2)NOTE: PLEASE SEE NEW REVISED SHEET | | | NOW SHOWS A NEW SUB PANEL. | | | PLEASE INCLUDE REVISED RISER DIAGRM FOR | | | NEW EQUIPMENT. | | | PLEASE ALSO INCLUDE PANEL SCHEDULES FOR | | | THIS TO SHOW MIN REQUIRED CIRCUITS PER | | | 2002 NEC. | | | PLEASEALSO INCLUDE LOAD CALC FOR NEW | | | A/C,SPA TUB,GEN LTS AND RECEPTS. | | | 215.5/ 220.31B | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|