| Plan Review Notes For Permit 03080399 |
| Permit Number |
03080399 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-11-04 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE COMMENTS FROM THE LAST | | | REVIEW WERE NOT ADDRESSED.PLEASE MAKE | | | THE FOLLOWING ADDITIONS AND OR NOTES TO | | | PLANS. | | | | | | 1} SHOW RECEPTACLE SPACING PER 210.52. | | | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 3} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | IN ADDITION TO THESE COMMENTS PLEASE | | | NOTE THAT ALL PLANS THAT ARE SIGNED AND | | | SEALED BY AN ENGINEER ARE REQUIRED PER | | | 61G15-23.002 TO HAVE A TITLE BLOCK. | | | THIS AND SIMILAR COMMENTS REGARDING NON | | | COMPLIANCE WITH ART 471 FS.STATUTES | | | HAVE COMPELLED US TO RETAIN ONE SET OF | | | PLANS TO BE FILED AND TURNED INTO THE | | | FPBE FOR SAID VIOLATIONS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|