| Date |
Text |
| 2003-11-08 00:00:00 | *****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS. |
| | |
| | 3.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #4, ENERGY CALCS REQUIRED FBC13-101.2. |
| | SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |
| | 4.)THIS IS AN IMPROVEMENT OF OVER |
| | 25% AND IS TO COMPLY WITH FBC3401.7.1.2. |
| | 1, 2003 AMENDMENT (SMOKE DETECTORS AND |
| | GFIS WHERE REQUIRED).THIS MAY BE |
| | ADDRESSED BY A NOTE ON THE PLAN; CONFIRM |
| | WITH THE ELECTRIC PLAN REVIEWER. |
| | |
| | 5.)NOTE THAT R4.2 WAS SPECIFIED IN THE |
| | WALL SECTION, NO ENERGY CALC SUBMITTED. |
| | IF A SHORT FORM IS SUBMITTED, R5 IS THE |
| | MINIMUM FOR AN EXTERIOR BLOCK WALL. |
| | |
| | 6.)SEE PREVIOUS LIST IN REGARDS TO |
| | IMPACT FEES, 233-5025. |
| | |
| | 7.)SEE PREVIOUS LIST, ITEM #13, SUBMIT |
| | A SECOND COPY OF THE HURRICANE SHUTTER |
| | PRODUCT APPROVAL.SUBMIT A HURRICANE |
| | SHUTTER INSTALLATION SCHEDULE, SEE |
| | ATTACHED. |
| | |
| | 8.)ADDITIONAL FEES DUE, BZ231208 WITH |
| | THE PREVIOUS CORRECTION LIST. |
| | |
| | 9.)THE ENGINEER'S TITLE BLOCK IS |
| | REQUIRED TO BE ON THE PLAN, FAC61G15-23. |
| | 002. |