Plan Review Notes
Plan Review Notes For Permit 03080399
Permit Number 03080399
Review Stop B
Sequence Number 2
Notes
Date Text
2003-11-08 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS.
  
 3.)SEE PREVIOUS CORRECTION LIST, ITEM
 #4, ENERGY CALCS REQUIRED FBC13-101.2.
 SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 4.)THIS IS AN IMPROVEMENT OF OVER
 25% AND IS TO COMPLY WITH FBC3401.7.1.2.
 1, 2003 AMENDMENT (SMOKE DETECTORS AND
 GFIS WHERE REQUIRED).THIS MAY BE
 ADDRESSED BY A NOTE ON THE PLAN; CONFIRM
 WITH THE ELECTRIC PLAN REVIEWER.
  
 5.)NOTE THAT R4.2 WAS SPECIFIED IN THE
 WALL SECTION, NO ENERGY CALC SUBMITTED.
 IF A SHORT FORM IS SUBMITTED, R5 IS THE
 MINIMUM FOR AN EXTERIOR BLOCK WALL.
  
 6.)SEE PREVIOUS LIST IN REGARDS TO
 IMPACT FEES, 233-5025.
  
 7.)SEE PREVIOUS LIST, ITEM #13, SUBMIT
 A SECOND COPY OF THE HURRICANE SHUTTER
 PRODUCT APPROVAL.SUBMIT A HURRICANE
 SHUTTER INSTALLATION SCHEDULE, SEE
 ATTACHED.
  
 8.)ADDITIONAL FEES DUE, BZ231208 WITH
 THE PREVIOUS CORRECTION LIST.
  
 9.)THE ENGINEER'S TITLE BLOCK IS
 REQUIRED TO BE ON THE PLAN, FAC61G15-23.
 002.