| Plan Review Notes For Permit 03080399 |
| Permit Number |
03080399 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMIN CODE | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT RE- | | | FLECT THE FLOOR PLAN. THE FLOOR PLAN | | | SHOWS A TUB AND THE RISER DIAGRAM SHOWS | | | A SHOWER. PLEASE CLAIRFY. (ALSO SEE RED | | | LINE CORRECTION TO RISER SHOWING CORRECT | | | ISOMETRIC). SECTION 104.2.1 | | | 2) SEE ATTACHED SHEET CONCERNING INFOR- | | | MATION REQUIRED PER 61G1-16.004. THIS | | | INFORMATION IS REQUIRED AND SHALL BE ON | | | EACH SHEET. PLEASE BE AWARE OF THIS FOR | | | FUTURE PLANS SUBMITTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|