| 2003-10-15 00:00:00 | *****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS. |
| | |
| | 3.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN (EXISTING, PROPOSED, NEW TOTAL). |
| | |
| | 4.)ENERGY CALCS REQUIRED FBC13-101.2. |
| | SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |
| | 5.)CHANGES DRAWN ON THE PLAN IN INK |
| | MUST BE INITIALED BY THE ENGINEER. |
| | |
| | 6.)SPECIFY WALL INSULATION S1-A1. |
| | |
| | 7.)NAILING FOR HETA20 CONFLICTS WITH |
| | THE CATALOG. |
| | |
| | 8.)LOWEST FLOOR ELEVATION AT THE |
| | PERIMETER OF A MONOLITHIC FOUNDATION |
| | SHALL BE A MINIMUM OF 4" ABOVE FINISH |
| | GRADE, CITY OF WEST PALM BEACH AMEND. TO |
| | THE FBC1804.1.7. |
| | |
| | 9.)WALL SECITON SHOWS A 16 X 12 |
| | MONO.FOOTING, CONFLICTS W/FLOOR PLAN. |
| | REVISE WALL SECTION. |
| | |
| | 10.) FLOOR PLAN GIVES A ROOM DESIGNATION |
| | OF "NEW MASTER BATHROOM".THIS ROOM IS |
| | 20X19 WITH EGRESS WINDOWS.IF THIS IS |
| | A BEDROOM, CORRECTLY LABEL THIS ROOM. |
| | |
| | 11.)WINDOW AT SHOWER AND TUB ARE |
| | REQUIRED TO BE SAFETY GLASS FBC2405.1. |
| | |
| | 12.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 13.)SUBMIT A SECOND COPY OF THE |
| | HURRICANE SHUTTER PRODUCT APPROVAL. |
| | |
| | 14.)ADDITIONAL FEES DUE, $249.52 |
| | (VALUE ADJUSTMENT AND RADON).SEE |
| | ATTACHED BZ231208. |