2003-10-15 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS.
  
 3.)PROVIDE AREA CALCULATIONS ON THE
 PLAN (EXISTING, PROPOSED, NEW TOTAL).
  
 4.)ENERGY CALCS REQUIRED FBC13-101.2.
 SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 5.)CHANGES DRAWN ON THE PLAN IN INK
 MUST BE INITIALED BY THE ENGINEER.
  
 6.)SPECIFY WALL INSULATION S1-A1.
  
 7.)NAILING FOR HETA20 CONFLICTS WITH
 THE CATALOG.
  
 8.)LOWEST FLOOR ELEVATION AT THE
 PERIMETER OF A MONOLITHIC FOUNDATION
 SHALL BE A MINIMUM OF 4" ABOVE FINISH
 GRADE, CITY OF WEST PALM BEACH AMEND. TO
 THE FBC1804.1.7.
  
 9.)WALL SECITON SHOWS A 16 X 12
 MONO.FOOTING, CONFLICTS W/FLOOR PLAN.
 REVISE WALL SECTION.
  
 10.) FLOOR PLAN GIVES A ROOM DESIGNATION
 OF "NEW MASTER BATHROOM".THIS ROOM IS
 20X19 WITH EGRESS WINDOWS.IF THIS IS
 A BEDROOM, CORRECTLY LABEL THIS ROOM.
  
 11.)WINDOW AT SHOWER AND TUB ARE
 REQUIRED TO BE SAFETY GLASS FBC2405.1.
  
 12.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 13.)SUBMIT A SECOND COPY OF THE
 HURRICANE SHUTTER PRODUCT APPROVAL.
  
 14.)ADDITIONAL FEES DUE, $249.52
 (VALUE ADJUSTMENT AND RADON).SEE
 ATTACHED BZ231208.