| Plan Review Notes For Permit 03080392 |
| Permit Number |
03080392 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS NOR DOES IT REFLECT | | | THE FLOOR PLAN. | | | A) ONLY THE FIXTURES WITHIN THE BATH- | | | ROOM GROUPS SHALL CONNECT TO THE WET- | | | VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. SEC 909.1 | | | WASH MACHINE & VEG. SINK SHALL NOT DRAIN | | | THRU BATHROOM PIPING. | | | B) KITCHEN SINK NOT VENTED. | | | C) NEW BAR SINK NOT SHOWN ON RISER. | | | D) EXTRA SHOWER UPSTREAM OF KITCHEN | | | SINK ON RISER. PLEASE CLAIRFY | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|