2003-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUPS SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SEC 909.1
 WASH MACHINE & VEG. SINK SHALL NOT DRAIN
 THRU BATHROOM PIPING.
 B) KITCHEN SINK NOT VENTED.
 C) NEW BAR SINK NOT SHOWN ON RISER.
 D) EXTRA SHOWER UPSTREAM OF KITCHEN
 SINK ON RISER. PLEASE CLAIRFY
  