Plan Review Notes
Plan Review Notes For Permit 03080392
Permit Number 03080392
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-15 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLAN AND RESUBMIT FOR REVIEW.
  
 1: THE EXISTING SERVICE IS INDICATED AS
 225 AMPS.THE 1/0 FEEDER CONDUCTORS ARE
 RATED FOR 175 AMPS,AND THE #4 GEC IS
 NOT LARGE ENOUGH FOR A 225 AMP
 SERVICE.PLEASE CORRELATE.
  
 2: PLEASE INDICATE WHERE THE OCP IS FOR
 THE "NEW PANEL".AGAIN PLEASE NOTE THE
 1/0 FEEDERS ARE RATED @ 175 AMPS,SEE
 RISER.THE SERVICE CALCULATION INDICATES
 A 200 AMP SERVICE.
  
 3: PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 4: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210.63.
  
 5: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 SEE REVIEWED SET.
  
 6: PLEASE NOTE KITCHEN COUNTER-
 SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 7: THE PANEL LOCATION IN THE GARAGE MUST
 COMPLY WITH 110.26.SEE 110.26(E) RE:
 HEAD SPACE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
  
 NOTE: PLEASE BRING THE REVIEWED SET IN
 WITH THE CORRECTED SET TO EXPEDITE THE
 REVIEW.