| 2003-08-15 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE NECESSARY CHANGES TO |
| | PLAN AND RESUBMIT FOR REVIEW. |
| | |
| | 1: THE EXISTING SERVICE IS INDICATED AS |
| | 225 AMPS.THE 1/0 FEEDER CONDUCTORS ARE |
| | RATED FOR 175 AMPS,AND THE #4 GEC IS |
| | NOT LARGE ENOUGH FOR A 225 AMP |
| | SERVICE.PLEASE CORRELATE. |
| | |
| | 2: PLEASE INDICATE WHERE THE OCP IS FOR |
| | THE "NEW PANEL".AGAIN PLEASE NOTE THE |
| | 1/0 FEEDERS ARE RATED @ 175 AMPS,SEE |
| | RISER.THE SERVICE CALCULATION INDICATES |
| | A 200 AMP SERVICE. |
| | |
| | 3: PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 4: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 5: PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210.63. |
| | |
| | 5: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | SEE REVIEWED SET. |
| | |
| | 6: PLEASE NOTE KITCHEN COUNTER- |
| | SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5. |
| | |
| | 7: THE PANEL LOCATION IN THE GARAGE MUST |
| | COMPLY WITH 110.26.SEE 110.26(E) RE: |
| | HEAD SPACE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | |
| | NOTE: PLEASE BRING THE REVIEWED SET IN |
| | WITH THE CORRECTED SET TO EXPEDITE THE |
| | REVIEW. |