| Plan Review Notes For Permit 03080349 |
| Permit Number |
03080349 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-11-20 00:00:00 | | | | | | | | | | | | | PASSED/PROVISO | | | | | | PASSED SUBJECT TO RESPONSE FROM RODNEY | | | COMPO CONCERNING REQUIREMENT FOR A | | | DILUTION TANK FOR CHEMICAL LAB. | | | NO PLUMBING SHALL BE INSTALLED UNTILL A | | | RESPONSE HAS BEEN ISSUED. IF A DILUTION | | | TANK IS REQUIRED THAN A REVISION WILL BE | | | REQUIRED WITH THE TANK INCLUDED. | | | | | | THE SERVICE SINK SHALL CONNECT DOWN- | | | STREAM OF THE BATHROOM GROUP. SECTION | | | 909.1 - A REVISION WILL BE REQUIRED FOR | | | THE RED LINE CORRECTION SHOWN ON THE | | | SANITARY RISER DIAGRAM. |
|