Plan Review Notes
Plan Review Notes For Permit 03080349
Permit Number 03080349
Review Stop M
Sequence Number 3
Notes
Date Text
2003-11-07 00:00:00PROVISO:2ND REQUEST
 1.PROVIDE MANUFACTURER SUBMITTAL FOR
 THE ROOF CURBS TO THE RTU'S.SEE
 ATTACHED REQUIREMENTS.
  
 PLEASE PROVIDE SUBMITTAL PRIOR TO
 ROUGH INSPECTION.
  
 2.CONDENSATE DRAIN SHALL COMPLY WITH
 2001 FBC(M) 307.2.1 #2 AND #3.
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED WITH NOTIFICATION TO ALARM
 STROBE IN NORMALLY OCCUPIED AREAS PER
 2001 FBC(M) 606.2.2 & NFPA 90A 4-4.4.3.
  