| Plan Review Notes For Permit 03080349 |
| Permit Number |
03080349 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-11-07 00:00:00 | PROVISO:2ND REQUEST | | | 1.PROVIDE MANUFACTURER SUBMITTAL FOR | | | THE ROOF CURBS TO THE RTU'S.SEE | | | ATTACHED REQUIREMENTS. | | | | | | PLEASE PROVIDE SUBMITTAL PRIOR TO | | | ROUGH INSPECTION. | | | | | | 2.CONDENSATE DRAIN SHALL COMPLY WITH | | | 2001 FBC(M) 307.2.1 #2 AND #3. | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED WITH NOTIFICATION TO ALARM | | | STROBE IN NORMALLY OCCUPIED AREAS PER | | | 2001 FBC(M) 606.2.2 & NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|