| 2003-11-06 00:00:00 | COMMENTS NOW ADDRESSED.PASSED |
| 2003-11-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 10/28/03: |
| | |
| | 3) FBC 11-4.15SHEET A2 HAS BEEN RED- |
| | LINED TO SHOW A MAXIMUM SPOUT HEIGHT OF |
| | 36" ABOVE FLOOR FOR THE WATER FOUNTAIN. |
| | |
| | 6) FBC 1601ANNOTATE THE PLANS TO |
| | SPECIFY THE RAFTER AND BEAM FASTENERS, |
| | AS PER THE 2003 SIMPSON CATALOGUE, FOR |
| | THE H16 ANCHORS NOW SPECIFIED AT EACH |
| | ROOF TRUSS ABOVE 'RECEIVING'. |
| | |
| | 7) FBC 1601ANNOTATE THE PLANS TO |
| | SPECIFY THE RAFTER AND LEDGER FASTENERS, |
| | AS PER THE 2003 SIMPSON CATALOGUE, FOR |
| | FOR THE LSU26 AND LSTA12 NOW SPECIFIED |
| | AT EACH CANOPY ROOF TRUSS. |
| | |
| | 13) NOTE: IF THE SUBMITTED PLANS ARE |
| | REVISED MANUALLY, EACH REVISION SHALL BE |
| | INITIALLED AND DATED. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |