Plan Review Notes
Plan Review Notes For Permit 03080349
Permit Number 03080349
Review Stop B
Sequence Number 3
Notes
Date Text
2003-11-06 00:00:00COMMENTS NOW ADDRESSED.PASSED
2003-11-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 10/28/03:
  
 3) FBC 11-4.15SHEET A2 HAS BEEN RED-
 LINED TO SHOW A MAXIMUM SPOUT HEIGHT OF
 36" ABOVE FLOOR FOR THE WATER FOUNTAIN.
  
 6) FBC 1601ANNOTATE THE PLANS TO
 SPECIFY THE RAFTER AND BEAM FASTENERS,
 AS PER THE 2003 SIMPSON CATALOGUE, FOR
 THE H16 ANCHORS NOW SPECIFIED AT EACH
 ROOF TRUSS ABOVE 'RECEIVING'.
  
 7) FBC 1601ANNOTATE THE PLANS TO
 SPECIFY THE RAFTER AND LEDGER FASTENERS,
 AS PER THE 2003 SIMPSON CATALOGUE, FOR
 FOR THE LSU26 AND LSTA12 NOW SPECIFIED
 AT EACH CANOPY ROOF TRUSS.
  
 13) NOTE: IF THE SUBMITTED PLANS ARE
 REVISED MANUALLY, EACH REVISION SHALL BE
 INITIALLED AND DATED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]