| Plan Review Notes For Permit 03080349 |
| Permit Number |
03080349 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1) FROM PREVIOUS REVIEW: CONTACT RODNEY | | | COMPO, ENVIRONMENTAL COMPLIANCE, (561) | | | 837-4074. A DILUTION TANK MAY BE REQUIR- | | | ED FOR THE CHEMICALS. | | | | | | 2) SHT A2 THE SANITARY RISER DIAGRAM | | | STILL DOES NOT REFLECT THE FLOOR PLAN. | | | THE LAV PAST THE EYEWASH IS NOT SHOWN | | | ON THE FLOOR PLAN. EYE WASH SHALL BE | | | DOWNSTREAM OF THE FLOOR DRAIN. NO LUNCH | | | ROOM SINK SHOWN ON THE RISER DIAGRAM. | | | THIS SHALL TIE INTO THE LINE FOR THE | | | DRINKING FOUNTAINS. | | | 3) SEPARATE GAS PERMIT REQUIRED FOR GAS | | | WORK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|