2003-10-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) FROM PREVIOUS REVIEW: CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE, (561)
 837-4074. A DILUTION TANK MAY BE REQUIR-
 ED FOR THE CHEMICALS.
  
 2) SHT A2 THE SANITARY RISER DIAGRAM
 STILL DOES NOT REFLECT THE FLOOR PLAN.
 THE LAV PAST THE EYEWASH IS NOT SHOWN
 ON THE FLOOR PLAN. EYE WASH SHALL BE
 DOWNSTREAM OF THE FLOOR DRAIN. NO LUNCH
 ROOM SINK SHOWN ON THE RISER DIAGRAM.
 THIS SHALL TIE INTO THE LINE FOR THE
 DRINKING FOUNTAINS.
 3) SEPARATE GAS PERMIT REQUIRED FOR GAS
 WORK.
  