Plan Review Notes
Plan Review Notes For Permit 03080349
Permit Number 03080349
Review Stop B
Sequence Number 2
Notes
Date Text
2003-10-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 8/22/03:
  
 3) FBC 11-4.15SHEET A2 HAS BEEN RED-
 LINED TO SHOW A MAXIMUM SPOUT HEIGHT OF
 36" ABOVE FLOOR FOR THE WATER FOUNTAIN.
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1606.2.4SPECIFY ANCHORS FOR THE
 SLOPED ROOF ABOVE 'RECEIVING'.THE WIND
 ENGINEERING / STRUCTURAL NOTES STILL DO
 NOT STATE THE DESIGN PRESSURES FOR THE
 ROOF STRUCTURE DESIGN.
  
 7) FBC 1601STRUCTURAL DETAILS FOR
 FASTENING OF THE NEW SLOPED CANOPIES.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.IT IS NOTED THAT SHEET A0,
 WIND ENGINEERING / STRUCTURAL NOTES,
 NOW INCLUDES A NOTE STATING THE UPLIFT
 (83 POUNDS) AT EACH TRUSS ANCHOR.THIS
 IS INSUFFICIENT FOR THE DESIGN WIND
 PRESSURES FOR THIS LOCATION.THE LSU24
 ANCHOR SPECIFIED ON SHEET S1
 (SECTION AA) IS NOT A VALID 2003 SIMPSON
 CATALOGUE REFERENCE.ALSO THE SPECIFIED
 RR RIDGE RAFTER CONNECTOR IS NOT
 SUITABLE FOR THIS APPLICATION.IT IS
 DESIGNED FOR RAFTER TO RIDGE CONNECTIONS
 (IN COMPRESSION) AND IS NOT APPROPRIATE
 FOR THE TENSILE LOADING THAT MUST BE
 RESISTED BE THE RAFTER IN MONOSLOPE
 CANOPY ROOF UNDER GRAVITY LOAD.SPECIFY
 VALID ANCHOR REFERENCES SUITABLE FOR THE
 APPLICABLE LOADING (TO INCLUDE THE
 DESIGN PRESSURES REFERENCED IN COMMENT 6
 ABOVE).
  
 13) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.