| 2003-09-02 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | NEC-99 |
| | FBC-2001 AMENDMENTS, CHAPTER |
| | ONE, ADMINSTRATION |
| | CODE. |
| | |
| | 1) SHT A2 INDICATE NATURE OF WORK BEING |
| | PERFORMED. LIST ALL CHEMICALS & HAZARD- |
| | OUS MATERIALS BEING USED. SUBMIT MSDS |
| | SHEETS FOR ALL CHEMICALS AND HAZARDOUS |
| | MATERIALS. AN EMERGENCY EYE WASH/SHOWER |
| | MAY BE REQUIRED AS A RESULT OF INFORMAT- |
| | ION RECIEVED FROM MSDS SHEETS. SECTION |
| | 104.2.1. |
| | 2) CONTACT RODNEY COMPO (561) 837-4074 |
| | OR MARIA ORTIZ (561) 837-4061. A DILUT- |
| | ION TANK MAY BE REQUIRED FOR THE CHEM- |
| | ICALS. |
| | 3) DETAIL REQUIRED FOR DRINKING FOUNTAIN |
| | PER 11-4.15, SPOUT HEIGHT 11-4.15.2, |
| | CLEARANCES/CLEAR FLOOR SPACE 11-4.15.5. |
| | ALSO PROVISIONS FOR THOSE WHO HAVE DIFF- |
| | ICULTY BENDING OR STOOPING PER SECTION |
| | 11-4.1.3(10)(A) |
| | 4) SHT A2 PLUMBING RISER, BREAK ROOM |
| | SINK SHALL CONNECT DOWNSTREAM OF THE |
| | TOILET ROOM FIXTURES. (SEE RED LINE |
| | CORRECTIONS) SECTION 909.1 |
| | 5) SHT A2 PLUMBING RISER DOES NOT RE- |
| | FLECT THE FLOOR PLAN. ONE SINK SHALL BE |
| | CONNECTED TO THE RIGHT SIDE OF THE BLDG. |
| | DRAIN. (SEE RED LINE CORRECTION) |
| | 6) A SERVICE SINK IS REQUIRED PER SECT- |
| | ION 403.1 |
| | 7) SECTION 422-17 NEC, PROTECTION OF |
| | COMBUSTABLE MATERIAL. EACH ELECTRICALLY |
| | HEATED APPLIANCE THAT IS INTENDED BY |
| | SIZE, WEIGHT, AND SERVICE TO BE LOCATED |
| | IN A FIXED POSITION SHALL BE PLACED SO |
| | AS TO PROVIDE AMPLE PROTECTION BETWEEN |
| | THE APPLIANCE AND ADJACENT COMBUSTIBLE |
| | MATERIAL. - THE ELECT. WATER HEATER |
| | SHALL BE IN A SEPARATE CLOSET OR A WALL |
| | 6" FROM W/H SHALL BE INSTALLED TO PRE- |
| | VENT STORAGE OF COMBUSTABLE MATERIAL |
| | FROM BEING PLACED NEXT TO THE HEATER. |
| | 8) SUBMIT DETAIL FOR BREAK ROOM SINK. |
| | SHOW COMPLIANCE WITH 11-4.24 AND ALL |
| | SUBSECTIONS. - CLEAR FLOOR SPACE - |
| | HEIGHT - KNEE CLEARANCE - DEPTH - EX- |
| | POSED PIPES & SURFACES - FAUCETS. |
| | 9) SHT S2 SUBMIT CALCULATIONS FOR ROOF |
| | DRAINS. SHOW SQUARE FOOTAGE OF ROOF AND |
| | ADD 1/2 AREA OF ALL VERTICAL WALLS IN- |
| | CLUDING PARAPET WALLS. IF GUTTER AND |
| | DOWNSPOUTS INDICATE SIZE OF DOWNSPOUTS |
| | & LOCATION. INDICATE SIZE OF GUTTER AND |
| | SLOPE PER SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. |
| | 10) APPLICATION INDICATES IRRIGATION |
| | WORK TO BE DONE. SEPARATE PERMIT/PLANS |
| | REQUIRED FOR IRRIGATION. |
| | 11) SHT A1, ALL REMOVED AND CAPPED |
| | PLUMBING LINES SHALL BE INSPECTED PRIOR |
| | TO COVERING. |
| | |