Date Text
2003-08-27 00:00:001) PLEASE INDICATE WHAT CHEMICALS WILL
 BE STORED IN THE CHEMICAL ROOM # 114.
 WILL THERE BE ANY FLAMMABLES,
 COMBUSTIBLES, CORROSIVES, TOXICS, ETC.
 PLEASE PROVIDE A COMPLETE LIST
 OF CHEMICALS AND STORAGE QUANTITIES.
 ALSO PLEASE INDICATE IF GASES, SOLIDS,
 OR LIQUIDS.
  
 2) PLEASE PROVIDE PRODUCT APPROVALS
 FOR 3086 POCKET ONE HOUR FIRE DOOR.
 PLEASE BE ADVISED THAT ALL FIRE RATED
 DOORS ARE REQUIRED TO BE EQUIPPED WITH
 SELF-CLOSING DEVICES.
  
 3) PLEASE DEFINE THE FOLLOWING TERMS
 GROSSING, EMBEDDING, H+E STAIN, SPECIAL
 STAIN.
  
 4) NO FIRE EXTINGUISHERS SHOWN ON THE
 PLANS.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 6) WHAT WILL BE STORED IN THE CLOSETS.
  
 7) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 8) WHAT WILL BE EXHAUSTED FROM THE HOOD
 LOCATED IN THE CHEM ROOM. A SEPARATE
 PLAN AND PERMIT WILL BE REQUIRED.
  
 9) WHAT IS THE PURPOSE 30" HIGH WORK
 BENCHES NEAR THE MAIN EXIT DOOR.
  
 10) PLEASE INDICATE OCCUPANT LOADS
 FOR THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL