| Plan Review Notes For Permit 03080349 |
| Permit Number |
03080349 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-25 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE 422.13 FOR SIZING OF | | | OCP FOR WATER HEATER. SHOWN AS 1P30A? | | | | | | 2)NOTE: PLEASE CORRELATE OCP/KW/AWG FOR | | | AHU'S AND COND UNITS. 424.3B | | | | | | 3)NOTE: PLEASE SEE CONDUCTORS FROM MAINS | | | TO PANELS. SHOWN AS #3'S. PLEASE SEE | | | 310.16 | | | | | | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 215.3/230.42 ETC | | | | | | 5)NOTE: PLEASE SUBMIT AIC RATING FOR | | | MAINS. 110.9 IT IS NOTED FOR BRANCH | | | BRKRS. | | | | | | 6)NOTE: PLEASE SEE 600.5 FOR REQ'D SIGN | | | CIRCUIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|