Plan Review Notes
Plan Review Notes For Permit 03080349
Permit Number 03080349
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 308.2.1 DECLARE ANY HAZARDOUS
 MATERIALS OR PROCESSES TO BE EMPLOYED/
 STORED IN LABORATORY FACILITY.
  
 2) FBC 11-4.13.6MANEUVERING CLEARANCE
 AT DOORS.THE DOORS BETWEEN 'RECEIVING'
 AND 'GROSSING' SHALL HAVE 18" CLEARANCE
 BETWEEN THE STRIKE EDGE OF THE DOORS
 AND THE ADJACENT WORK BENCH ON THE PULL
 SIDE OF THE DOORS FOR ACCESSIBILITY.
 REF. FIG. 27A
  
 3) FBC 11-4.15 AMEND THE PLANS TO SHOW
 THE REQUIRED ACCESSIBILITY HEIGHTS AND
 CLEARANCES AT THE WATER FOUNTAIN.
 REF. FIG. 27
  
 4) FBC* 104.2.1SUBMIT DETAILS FOR THE
 PROPOSAL TO RAISE THE FOOR LEVEL OF THE
 EXISTING BUILDING.
  
 5) FBC* 104.2.1.2SUBMIT MANUFACTURER'S
 DETAILS TO JUSTIFY THE STATED ONE-HOUR
 FIRE-RATING OF THE 'CHEM ROOM' POCKET
 DOOR.
  
 6) FBC 1606.2.4SPECIFY ANCHORS FOR THE
 SLOPED ROOF.THE WIND ENGINEERING AND
 STRUCTURAL NOTES DO NOT STATE THE DESIGN
 WIND PRESSURES FOR THE ROOF.
  
 7) FBC 1601SUBMIT STRUCTURAL DETAILS
 FOR FASTENING OF THE NEW SLOPED
 CANOPIES.IS THERE AN EXISTING CONCRETE
 CANOPY AT EACH LOCATION (THE AS-BUILT
 PLAN DOES NOT SHOW THEM)?
  
 8) FBC 1707.4SUBMIT PRODUCT APPROVALS
 FOR THE NEW WINDOWS AND EXTERIOR DOORS.
  
 9) FBC* F102.2.4ALL ROOF COVERINGS IN
 THE FIRE DISTRICT SHALL CONFORM TO THE
 REQUIREMENTS OF CLASS A OR B ROOF
 COVERINGS AS DEFINED IN FBC 1505.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE FOR BOTH THE RE-ROOF AND THE
 NEW STANDING SEAM ROOF WHICH SHALL BE
 LISTED AS CLASS A OR B BY AN APPROVED
 TESTING AGENCY, OR SHALL MEET THE
 THICKNESS/GAUGE/WEIGHT CRITERIA
 SPECIFIED IN TABLE FBC 1507.3.9.2
  
 10) FBC* F102.2.7ARCHITECTURAL TRIM ON
 BUILDINGS IN THE FIRE DISTRICT SHALL BE
 CONSTRUCTED OF APPROVED NON-COMBUSTIBLE
 MATERIALS.THE SIDING SHOWN ON THE
 ELEVATIONS (SHEET A3) IS STATED AS BOTH
 "HADIE-PLANK" AND "HARDIE-PLANK".IN
 THE REVIEW IT HAS BEEN ASSUMED THAT THE
 PROPOSED SIDING IS 'HARDIPLANK' (KNOWN
 TO BE NON-COMBUSTIBLE) BY JAMES HARDIE
 SIDING PRODUCTS.PLEASE ADVISE IF THIS
 ASSUMPTION IS NOT CORRECT.ANNOTATE THE
 PLANS.
  
 11) FBC* F102.2.8IN THE FIRE DISTRICT,
 CANOPIES SHALL BE OF NON-COMBUSTIBLE
 MATERIAL OR FIRE-RETARDANT WOOD.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE
  
 12) FBC* F102.2.9ROOF MOUNTED
 MECHANICAL EQUIPMENT.SUPPORTS FOR
 EQUIPMENT PLACED ABOVE THE ROOF OF ANY
 BUILDING WITHIN THE FIRE DISTRICT SHALL
 BE OF NON-COMBUSTIBLE CONSTRUCTION.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 13) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]