| Date |
Text |
| 2003-08-22 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC 308.2.1 DECLARE ANY HAZARDOUS |
| | MATERIALS OR PROCESSES TO BE EMPLOYED/ |
| | STORED IN LABORATORY FACILITY. |
| | |
| | 2) FBC 11-4.13.6MANEUVERING CLEARANCE |
| | AT DOORS.THE DOORS BETWEEN 'RECEIVING' |
| | AND 'GROSSING' SHALL HAVE 18" CLEARANCE |
| | BETWEEN THE STRIKE EDGE OF THE DOORS |
| | AND THE ADJACENT WORK BENCH ON THE PULL |
| | SIDE OF THE DOORS FOR ACCESSIBILITY. |
| | REF. FIG. 27A |
| | |
| | 3) FBC 11-4.15 AMEND THE PLANS TO SHOW |
| | THE REQUIRED ACCESSIBILITY HEIGHTS AND |
| | CLEARANCES AT THE WATER FOUNTAIN. |
| | REF. FIG. 27 |
| | |
| | 4) FBC* 104.2.1SUBMIT DETAILS FOR THE |
| | PROPOSAL TO RAISE THE FOOR LEVEL OF THE |
| | EXISTING BUILDING. |
| | |
| | 5) FBC* 104.2.1.2SUBMIT MANUFACTURER'S |
| | DETAILS TO JUSTIFY THE STATED ONE-HOUR |
| | FIRE-RATING OF THE 'CHEM ROOM' POCKET |
| | DOOR. |
| | |
| | 6) FBC 1606.2.4SPECIFY ANCHORS FOR THE |
| | SLOPED ROOF.THE WIND ENGINEERING AND |
| | STRUCTURAL NOTES DO NOT STATE THE DESIGN |
| | WIND PRESSURES FOR THE ROOF. |
| | |
| | 7) FBC 1601SUBMIT STRUCTURAL DETAILS |
| | FOR FASTENING OF THE NEW SLOPED |
| | CANOPIES.IS THERE AN EXISTING CONCRETE |
| | CANOPY AT EACH LOCATION (THE AS-BUILT |
| | PLAN DOES NOT SHOW THEM)? |
| | |
| | 8) FBC 1707.4SUBMIT PRODUCT APPROVALS |
| | FOR THE NEW WINDOWS AND EXTERIOR DOORS. |
| | |
| | 9) FBC* F102.2.4ALL ROOF COVERINGS IN |
| | THE FIRE DISTRICT SHALL CONFORM TO THE |
| | REQUIREMENTS OF CLASS A OR B ROOF |
| | COVERINGS AS DEFINED IN FBC 1505. |
| | ANNOTATE THE PLANS TO DEMONSTRATE |
| | COMPLIANCE FOR BOTH THE RE-ROOF AND THE |
| | NEW STANDING SEAM ROOF WHICH SHALL BE |
| | LISTED AS CLASS A OR B BY AN APPROVED |
| | TESTING AGENCY, OR SHALL MEET THE |
| | THICKNESS/GAUGE/WEIGHT CRITERIA |
| | SPECIFIED IN TABLE FBC 1507.3.9.2 |
| | |
| | 10) FBC* F102.2.7ARCHITECTURAL TRIM ON |
| | BUILDINGS IN THE FIRE DISTRICT SHALL BE |
| | CONSTRUCTED OF APPROVED NON-COMBUSTIBLE |
| | MATERIALS.THE SIDING SHOWN ON THE |
| | ELEVATIONS (SHEET A3) IS STATED AS BOTH |
| | "HADIE-PLANK" AND "HARDIE-PLANK".IN |
| | THE REVIEW IT HAS BEEN ASSUMED THAT THE |
| | PROPOSED SIDING IS 'HARDIPLANK' (KNOWN |
| | TO BE NON-COMBUSTIBLE) BY JAMES HARDIE |
| | SIDING PRODUCTS.PLEASE ADVISE IF THIS |
| | ASSUMPTION IS NOT CORRECT.ANNOTATE THE |
| | PLANS. |
| | |
| | 11) FBC* F102.2.8IN THE FIRE DISTRICT, |
| | CANOPIES SHALL BE OF NON-COMBUSTIBLE |
| | MATERIAL OR FIRE-RETARDANT WOOD. |
| | ANNOTATE THE PLANS TO DEMONSTRATE |
| | COMPLIANCE |
| | |
| | 12) FBC* F102.2.9ROOF MOUNTED |
| | MECHANICAL EQUIPMENT.SUPPORTS FOR |
| | EQUIPMENT PLACED ABOVE THE ROOF OF ANY |
| | BUILDING WITHIN THE FIRE DISTRICT SHALL |
| | BE OF NON-COMBUSTIBLE CONSTRUCTION. |
| | ANNOTATE THE PLANS TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 13) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |