| 2003-11-25 00:00:00 | DENIED; | | | 1.SHOW MINIMUM PLUMBING FACILITIES TO | | | JUSTIFY REMOVEL OF ONE LAV. AND ONE | | | TOILET FROM THE FEMALE RESTROOM SEE | | | SEC.403.1.1.2 AND 403.3.3. | | | 2.PLUMBING FIXTURE LEGEND. | | | A.EWC CALL FOR TWO LEVEL DRINKING | | | FOUNTAIN FLOOR PLAN SHOWS SINGLE | | | LEVEL. | | | B.MOP SINK STILL ON LEGEND, FLOOR | | | PLAN DOES NOT SHOW LOCATION. | | | 3.DETAIL EWH RISER DIAGRAM. REMOVE IF | | | WATER HEATER IS NOT BEING MOVER. FOR | | | POINT OF REFERENCE WHERE IS WATER | | | HEATER? | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|