| 2003-09-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 AMENDMENTS, CHAPTER |
| | ONE, ADMIN. CODE |
| | |
| | 1) SHT A2.1 PER TABLE 403.1 A DRINKING |
| | FOUNTAIN IS REQUIRED. (ALSO SEE SECTION |
| | 410.1) |
| | 2) SHT P-1 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL IS REQUIRED PER SECT- |
| | ION 607.3.2 |
| | 3) SHT P-2 PLUMBING FIXTURE SCHEDULE, |
| | ITEMS P-10, P-11, P-12, P-13, & P-17 NOT |
| | FOUND ON FLOOR PLAN. PLEASE CLAIRFY. |
| | SECTION 104.2.1 |
| | 4) SHT P-2 FLOOR DRAINS NOT APPROVED FOR |
| | INDIRECT WASTE. FLOOR SINKS ARE REQUIRED |
| | PER SECTION 802.3 |
| | 5) SHT P-3 AN RPZ BACKFLOW IS REQUIRED |
| | ON WATER SERVICE FOR THIS SPACE. UTILITY |
| | ORD. & SECTION 608.13.2 |
| | 6) SHT P-3 FILTER FOR REFERIGERATOR ICE |
| | MAKER SHALL BE NSF APPROVED. PLEASE SUB- |
| | MIT MANUFACTURE SPECIFICATIONS. SECTION |
| | 611.1. (SEE ATTACHED SHEET) |
| | 7) SHT P-4 ITEM #10 BOOSTER PUMP, MANUF. |
| | SPEC. SHEETS REQUIRED. PUMP SHALL BE |
| | LISTED. SECTION 303.4 |
| | 8) SHT P-4 ITEM #8 BACKFLOWS, MAXIMUM |
| | HEIGHT 4' ABOVE THE FLOOR FOR SERVICING |
| | AND CERTIFYING. |
| | 9) SHT P-5 DOMESTIC WATER ISOMETRIC. THE |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE |
| | NOT AT THE TOP OF THE DROPS IN THE CEIL- |
| | ING AS SHOWN. MANUF. INSTALLATION INSTR- |
| | UCTIONS AND PDI-WH 201. |
| | 10) ALL DEVICES, APPURTENANCES. APPLIAN- |
| | CES AND APPARATUS INTENDED TO SERVE SOME |
| | SPACIAL FUNCTION, SUCH AS STERILIZATION, |
| | DISTILLATION, PROCESSING, COOLING, OR |
| | STORAGE OF ICE OR FOODS, AND THAT CONN- |
| | ECT TO EIGHER THE WATER SUPPLY OR DRAIN- |
| | AGE SYSTEM, SHALL BE PROVIDED WITH PRO- |
| | TECTION AGAINST BACKFLOW, FLOODING, |
| | FOWLING, CONTAMINATION OF THE WATER SUP- |
| | PLY SYSTEM AND STOPPAGE OF THE DRAIN. |
| | SECTION 422.3 |
| | |
| | REVIEW BY KEN STEVENS |