Plan Review Notes
Plan Review Notes For Permit 03080291
Permit Number 03080291
Review Stop P
Sequence Number 1
Notes
Date Text
2003-09-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) SHT A2.1 PER TABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED. (ALSO SEE SECTION
 410.1)
 2) SHT P-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED PER SECT-
 ION 607.3.2
 3) SHT P-2 PLUMBING FIXTURE SCHEDULE,
 ITEMS P-10, P-11, P-12, P-13, & P-17 NOT
 FOUND ON FLOOR PLAN. PLEASE CLAIRFY.
 SECTION 104.2.1
 4) SHT P-2 FLOOR DRAINS NOT APPROVED FOR
 INDIRECT WASTE. FLOOR SINKS ARE REQUIRED
 PER SECTION 802.3
 5) SHT P-3 AN RPZ BACKFLOW IS REQUIRED
 ON WATER SERVICE FOR THIS SPACE. UTILITY
 ORD. & SECTION 608.13.2
 6) SHT P-3 FILTER FOR REFERIGERATOR ICE
 MAKER SHALL BE NSF APPROVED. PLEASE SUB-
 MIT MANUFACTURE SPECIFICATIONS. SECTION
 611.1. (SEE ATTACHED SHEET)
 7) SHT P-4 ITEM #10 BOOSTER PUMP, MANUF.
 SPEC. SHEETS REQUIRED. PUMP SHALL BE
 LISTED. SECTION 303.4
 8) SHT P-4 ITEM #8 BACKFLOWS, MAXIMUM
 HEIGHT 4' ABOVE THE FLOOR FOR SERVICING
 AND CERTIFYING.
 9) SHT P-5 DOMESTIC WATER ISOMETRIC. THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF THE DROPS IN THE CEIL-
 ING AS SHOWN. MANUF. INSTALLATION INSTR-
 UCTIONS AND PDI-WH 201.
 10) ALL DEVICES, APPURTENANCES. APPLIAN-
 CES AND APPARATUS INTENDED TO SERVE SOME
 SPACIAL FUNCTION, SUCH AS STERILIZATION,
 DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT CONN-
 ECT TO EIGHER THE WATER SUPPLY OR DRAIN-
 AGE SYSTEM, SHALL BE PROVIDED WITH PRO-
 TECTION AGAINST BACKFLOW, FLOODING,
 FOWLING, CONTAMINATION OF THE WATER SUP-
 PLY SYSTEM AND STOPPAGE OF THE DRAIN.
 SECTION 422.3
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]