| 2003-08-21 00:00:00 | 1) FIRE ALARM NOTES # 17 AND # 19 ARE | | | INCORRECT. DUCT SMOKE DETECTORS ARE | | | REQUIRED TO ACTIVATE THE FIRE ALARM | | | SYSTEM AND THE CIRCUITS AND DEVICES | | | SHALL BE CLASS A, STYLE D. SEPARATE | | | PLANS AND PERMITS REQUIRED FOR FIRE | | | ALARM EQUIPMENT REMODEL. | | | | | | 2) PLEASE INDICATE HOW THE ELECTRIC | | | STRIKE MECHANISMS EFFECT EXITING. | | | | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE SPRINKLER REMODEL. | | | | | | 4) DOORS 105B AND 106B OPEN INTO THE | | | CORRIDOR AND REDUCES IT DOWN TO MORE | | | THAN 50 PERCENT. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|