| Plan Review Notes For Permit 03080273 |
| Permit Number |
03080273 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-21 00:00:00 | *****CORRECTIONS****** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)ENERGY CALCS INCORRECT; SHOWS AN | | | UNDER ATTIC SPACE OF 186 SQUARE FEET. | | | PLEASE SEE THE PLAN AND REVISE THE | | | ENERGY CALCS TO MATCH. | | | | | | 2.)ADDITIONAL FEES DUE (RADON), $4.50, | | | BZ231393. | | | | | | 3.)SEPARATE PERMITS REQUIRED. | | | | | | 4.)SEE PREVIOUS LIST, ITEM #12. STAIRS | | | SHALL HAVE FLOOR OR LANDINGS AT DOOR | | | OPENINGS, FBC1007.4.2. | | | | | | 5.)PREVIOUS LIST ITEM #13 WAS | | | ADDRESSED ON THE FOUNDATION PLAN BUT | | | THE TREAD IS SHOWN AS 10" (RATHER THAN | | | 16") ON SHEETS AS1 AND A1.REVISE SO | | | THAT ALL DETAILS ARE CONSISTENT AND | | | COMPLY WITH FBC1007.3. | | | | | | 6.)SEE PREVIOUS LIST ITEM #14.A NOTE | | | WAS MADE ON THE PLAN IN REGARDS TO | | | IMPACT PROTECTION BUT THE PRODUCT | | | APPROVALS FOR IMPACT PROTECTION FOR THE | | | GLAZED DOOR (AND ANY WINDOWS NOT IMPACT | | | RESISTANT) WERE NOT SUBMITTED.SUBMIT | | | TWO COPIES AND THE ATTACHED SHEDULE, | | | OR A SEPARATE PERMIT FOR IMPACT | | | PROTECTION WILL BE REQUIRED. | | | | | | 7.)SEE PREVIOUS LIST, ITEM #17, NOT | | | ADDRESSED.A SOILS INVESTIGATION | | | REPORT IS REQUIRED. | | | | | | 8.)SEE ATTACHED IN REGARDS TO | | | FS553.80(2)(B). |
|