| 2003-08-12 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES ON | | | THE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PROVIDE A SCHEDULE FOR "MB" PANEL. | | | | | | 3} PANEL "E" HAS AN OCP AND FEED FOR | | | PANEL"C",THE RISER SHOWS IT BEING FED | | | FROM "MB",PLEASE CORRELATE. | | | | | | 4} PANEL "A" DOES NOT SHOW 2 SMALL | | | APPLIANCE CIRCUITS TO COMPLY WITH | | | 210.52(B)(3),AND 220.16(A). | | | | | | 5} THE LOCATION OF PANEL "E" DOES NOT | | | APPEAR TO COMPLY WITH 110.26.THE A/C | | | COMPRESSER WOULD BE IN THE WAY. | | | | | | 6} IF THE EXISTING "GUEST HOUSE" IS | | | DETACHED,PANEL "B" MUST COMPLY WITH | | | 225.31 & 250.32.PLEASE SHOW SAME ON | | | RISER. | | | | | | NOTE: OUR CURRENTLY ADOPTED EDITION OF | | | THE NEC IS 2002.(SEE NOTE #2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|