Plan Review Notes
Plan Review Notes For Permit 03080273
Permit Number 03080273
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-12 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PROVIDE A SCHEDULE FOR "MB" PANEL.
  
 3} PANEL "E" HAS AN OCP AND FEED FOR
 PANEL"C",THE RISER SHOWS IT BEING FED
 FROM "MB",PLEASE CORRELATE.
  
 4} PANEL "A" DOES NOT SHOW 2 SMALL
 APPLIANCE CIRCUITS TO COMPLY WITH
 210.52(B)(3),AND 220.16(A).
  
 5} THE LOCATION OF PANEL "E" DOES NOT
 APPEAR TO COMPLY WITH 110.26.THE A/C
 COMPRESSER WOULD BE IN THE WAY.
  
 6} IF THE EXISTING "GUEST HOUSE" IS
 DETACHED,PANEL "B" MUST COMPLY WITH
 225.31 & 250.32.PLEASE SHOW SAME ON
 RISER.
  
 NOTE: OUR CURRENTLY ADOPTED EDITION OF
 THE NEC IS 2002.(SEE NOTE #2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718