| 2003-08-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424 | | | | | | 1) SHT 3 OF 5 MAIN DRAIN DETAIL SHOWS | | | A PVC SUCTION LINE. SEC 424.1.6.5.10.5 | | | CALLS FOR MAIN DRAIN TO BE CONNECTED TO | | | A COLLECTOR TANK. PLEASE CLAIRFY IF THIS | | | WILL BE GRAVITY DRAINED OR SUCTION. | | | 2) SEC 424.1.6.5.14 A SKETCH OF ANY PRO- | | | POSED HEATER INSTALLATION INCLUDING | | | VALVES, THERMOMETER, PIPE SIZES AND | | | MATERIAL SPECIFICATIONS SHALL BE INCLUD- | | | ED IN THE APPLICATION FOR PERMIT PRIOR | | | TO INSTALLATION. | | | 3) PUMPS SHALL BE EQUIPPED WITH A HAIR & | | | LINT STRAINER. SEC 424.1.6.5.4 | | | 4) SHT 4 OF 5 VALVES AND PIPE SIZE CHART | | | (M) INDICATES A POOL HEATER. HEATER | | | SHALL BE LABELED PER SECTION 303.4 OF | | | FBC-2001 PLUMBING. SUBMIT MANUF. INFO. | | | SPECIFICATIONS SHEETS. | | | 5) PLASTIC PIPE SUBJECT TO A PERIOD OF | | | PROLONGED SUNLIGHT EXPOSURE SHALL BE | | | COATED TO PROTECT IT FROM ULTRAVIOLET | | | LIGHT DEGRADATION. SEC 424.1.6.5.6 | | | 6) ALL WATER HEATING EQUIPMENT SHALL BE | | | INSTALLED WITH FLANGES OR UNION CONNECT- | | | IONS ADJACENT TO THE HEATER. SECTION | | | 424.1.6.5.14. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|