Date Text
2003-08-15 00:00:00DENIED
 REFERENCE: FBC-2001 424
  
 1) SHT 3 OF 5 MAIN DRAIN DETAIL SHOWS
 A PVC SUCTION LINE. SEC 424.1.6.5.10.5
 CALLS FOR MAIN DRAIN TO BE CONNECTED TO
 A COLLECTOR TANK. PLEASE CLAIRFY IF THIS
 WILL BE GRAVITY DRAINED OR SUCTION.
 2) SEC 424.1.6.5.14 A SKETCH OF ANY PRO-
 POSED HEATER INSTALLATION INCLUDING
 VALVES, THERMOMETER, PIPE SIZES AND
 MATERIAL SPECIFICATIONS SHALL BE INCLUD-
 ED IN THE APPLICATION FOR PERMIT PRIOR
 TO INSTALLATION.
 3) PUMPS SHALL BE EQUIPPED WITH A HAIR &
 LINT STRAINER. SEC 424.1.6.5.4
 4) SHT 4 OF 5 VALVES AND PIPE SIZE CHART
 (M) INDICATES A POOL HEATER. HEATER
 SHALL BE LABELED PER SECTION 303.4 OF
 FBC-2001 PLUMBING. SUBMIT MANUF. INFO.
 SPECIFICATIONS SHEETS.
 5) PLASTIC PIPE SUBJECT TO A PERIOD OF
 PROLONGED SUNLIGHT EXPOSURE SHALL BE
 COATED TO PROTECT IT FROM ULTRAVIOLET
 LIGHT DEGRADATION. SEC 424.1.6.5.6
 6) ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION CONNECT-
 IONS ADJACENT TO THE HEATER. SECTION
 424.1.6.5.14.
  
 REVIEW BY KEN STEVENS