| 2003-09-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMIN. CODE | | | | | | 1) SEPARATE PLUMBING PERMIT REQUIRED | | | 2) SHT A-1 WASH MACHINE REQUIRES A TRAP, | | | AND STANDPIPE. SECTIONS 1002.1 & 802.4 | | | 3) CLEANOUT REQUIRED ON W/M STACK 4 FEET | | | ABOVE THE FLOOR. 708.10. | | | 4) THE PERSONAL SEAL, SIGNATURE, AND | | | DATE SHALL APPEAR ON SHEETS. NO DATE | | | WHERE SIGNED AND SEALED. 61G1-16.003 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|