Plan Review Notes
Plan Review Notes For Permit 03080097
Permit Number 03080097
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-21 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} INDICATE COMPLIANCE WITH 250-50 FOR
 THE GEC SYSTEM AND SIZE OF CONDUCTOR.
  
 3} THE ELECTRICAL FLOOR PLANS DO NOT
 MATCH THE ARCHITECTURAL FLOOR
 PLAN,PLEASE CORRELATE.
  
 5} PROVIDE A LOAD CALCULATION AND PANEL
 SCHEDULE PER 215.5 NEC.INDICATE REQUIRED
 CIRCUITS ON SAME.
  
 6} PLEASE SEE THE 2002 NEC FOR
 ELECTRICAL REQUIREMENTS AND
 NFPA-72,1999,FOR SMOKE DETECTION
 DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718