| Plan Review Notes For Permit 03080097 |
| Permit Number |
03080097 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-21 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES ON | | | PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} INDICATE COMPLIANCE WITH 250-50 FOR | | | THE GEC SYSTEM AND SIZE OF CONDUCTOR. | | | | | | 3} THE ELECTRICAL FLOOR PLANS DO NOT | | | MATCH THE ARCHITECTURAL FLOOR | | | PLAN,PLEASE CORRELATE. | | | | | | 5} PROVIDE A LOAD CALCULATION AND PANEL | | | SCHEDULE PER 215.5 NEC.INDICATE REQUIRED | | | CIRCUITS ON SAME. | | | | | | 6} PLEASE SEE THE 2002 NEC FOR | | | ELECTRICAL REQUIREMENTS AND | | | NFPA-72,1999,FOR SMOKE DETECTION | | | DEVICES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|