| 2003-08-21 00:00:00 | THESE COMMENTS ARE ALSO FOR PHASE 2,3, |
| | AND 4 FOR THE PROJECT. |
| | |
| | 1) TEMPORARY WALLS AND DUST PROTECTION |
| | SHALL BE CONSTRUCTED OF NON-COMBUSTIBLE |
| | MATERIALS. NON FIRE RETARDANT VISQUEEN |
| | SHALL NOT BE PERMITTED. |
| | |
| | 2) TEMPORARY EGRESS AND EXIT CORRIDORS |
| | SHALL MEET ALL APPLICABLE CODES. |
| | |
| | 3) ALL RENOVATIONS SHALL COMPLY WITH |
| | NFPA 241. |
| | |
| | 4) ALL TEMPORARY CONSTRUCTION |
| | MATERIALS SHALL NOT INTERFERE WITH |
| | ANY EXISTING FIRE PROTECTION FEATURES. |
| | |
| | 5) PLEASE INDICATE IN WRITING HOW THE |
| | HOTEL WILL REMAIN OPEN DURING |
| | CONSTRUCTION. ALSO PLEASE INDICATE |
| | IN WRITING WHAT SAFEGAURDS WILL BE |
| | TAKEN TO SEPARATE CONSTRUCTION FROM |
| | NON-CONSTRUCTION AREAS. ALSO HOW WILL |
| | EXITS, EXIT ACCESS AND EXIT DISCHARGE |
| | BE MAINTAINED DURING RENOVATION |
| | PERIODS. |
| | |
| | 6) DOOR SCHEDULE NOTES INDICATE |
| | UNDERCUTTING OF GUESTROOM ENTRY DOORS |
| | WHICH ARE 20 MINUTE FIRE RATED. PLEASE |
| | EXPLAIN NOTE RATIONALE. |
| | |
| | 7) COMBUSTIBLE DEBRIS IS TO BE REMOVED |
| | DAILY DURING DEMOLITION ACTIVITIES. |
| | |
| | 8) A NEW FIRE ALARM SYSTEM WAS |
| | RECENTLY INSTALLED WITHIN THE HOTEL |
| | EXCEPT FOR THE FIRST FLOOR. THE FIRE |
| | ALARM SYSTEM IS TO BE UPGRADED ON THE |
| | ENTIRE FIRST FLOOR. |
| | |
| | 9) THE RAMP ON SERVICE CORRIDOR # 4 |
| | SHALL BE EQUIPPED WITH HANDRAILS ON |
| | BOTH SIDES. |
| | |
| | 10) FABRIC CANOPIES SHALL BE FIRE RATED |
| | SINCE THE HOTEL IS LOCATED IN THE |
| | CITY FIRE LIMITS. |
| | |
| | 11) ALL ARCHITECTURAL TRIM SHALL BE |
| | NON-COMBUSTIBLE AS REQUIRED IN |
| | APPENDIX F, LOCAL AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 12) BUILDING ADDRESS REQUIRED. |
| | |
| | 13) THE FURNITURE PLAN APPEARS THAT |
| | SEATING WITHIN THE RESTAURANT 001, |
| | AND LOUNGE 041 APPEAR TO BE TOO |
| | CLOSE TOGETHER. |
| | |
| | 14) ALL NEW STAIRS AND RAMPS SHALL |
| | BE EQUIPPED WITH HANDRAILS. |
| | |
| | 15) SEPARATE PLANS AND PERMITS |
| | REQUIRED FOR THE NEW HOOD PLANNED |
| | FOR KITCHEN 002. |
| | |
| | 16) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR THE FIRE SPRINKLER REMODEL. |
| | |
| | 17) ANY FIRE WALLS DISCOVERED TO HAVE |
| | DAMAGE ARE TO BE REPAIRED. |
| | |
| | 18) ALL WOOD IS REQUIRED TO BE FRT. |
| | EXTERIOR GRADE PLYWOOD IS NOT |
| | ACCEPTABLE SINCE THE BUILDING IS LOCATED |
| | IN THE FIRE LIMITS. |
| | |
| | 19) ALL AREAS USED FOR EXITING SHALL |
| | BE A MINIMUM OF AT LEAST SEVEN FEET |
| | HIGH. |
| | |
| | 20) ENSURE THAT ALL EXISTING SMOKE |
| | DETECTORS IN EACH GUEST ROOM IS IN |
| | WORKING ORDER. |
| | |
| | 21) PLEASE INDICATE IN WRITING HOW THE |
| | NEW FIRE SPRINKLER SYSTEM HEADS WILL |
| | BE INSTALLED AND PROTECTION STILL BE |
| | PROVIDED WITHIN THE HOTEL. |
| | |
| | 22) PLEASE NOTE ON THE PLANS THE |
| | SIZES OF THE BATRHROOMS AND CLOSETS |
| | THAT WILL NOT BE RECEIVING FIRE |
| | SPRINKLER PROTECTION. |
| | |
| | 23) PLEASE NOTE ON THE PLANS THE |
| | LOCATIONS OF ALL EXISTING SYSTEM |
| | SMOKE AND NON SYSTEM SMOKE DETETECTORS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |