| Plan Review Notes For Permit 03080042 |
| Permit Number |
03080042 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-09-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA STATUTES | | | FBC-2001 AMENDMENTS, CHAPTER | | | ONE, ADMIN. CODE | | | | | | 1) SHTS MP060 & MP061 ALL TERMINATED OR | | | CAPPED PLUMBING LINES TO BE INSPECTED | | | PRIOR TO COVERING. | | | 2) SHT MP060 CLAIRFICATION REQUIRED FOR | | | G.W. LINE CAP OFF. (PASSES THROUGH KEY | | | CAFE RESTURANT. | | | 3) SHT MP201 DETAIL 1/MP202 ON SHEET | | | MP201? PLEASE CLAIRFY. | | | 4) SHT MP-201 DETAIL 3/MP201 FOR SECOND | | | FLOOR. 2ND FLOOR NOT IN PHASE 2 AS IN- | | | DICATED ON APPLICATION. NO 2ND FLOOR | | | FLOOR PLANS SHOWN. | | | 5) SHT MP201 DETAIL 4/201 NOT FOUND ON | | | FLOOR PLAN. PLEASE CLAIRFY. | | | 6) SANITARY RISER DIAGRAMS AND WATER | | | RISER DIAGRAMS REQUIRED PER SECTION | | | 104.2.1 | | | 7) 61G1-16.004(2) FIRM LICENSE NUMBER | | | REQUIRED ON TITLE BLOCK FOR EACH SHEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|