Plan Review Notes
Plan Review Notes For Permit 03080042
Permit Number 03080042
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-20 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 EM.EXT LTS PER 700.12E.
  
 2)NOTE: PLEASE SUBMIT FIXTURE SCHEDULES
 CONTAINING WATTAGES/VOLTAGES FOR FIXTURE
 -S.
  
 3)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH SUBMITTED PANEL SCHEDULES/
 MAX LOAD PER CIRCUIT.
 A COMPLETE AND ACCURATE PANEL SCHEDULES
 WILL BE REQ'D BEFORE FINAL ALSO.
  
 4)NOTE: PLEASE INCLUDE LOADS ON PANELS
 215.5
  
  
 5)NOTE: PLEASE SEE ATTACHED COPIES OF
 FAC 61G15-23.002 FOR ENGINEERS AND
 61G1-16.004 FOR ARCH'S. PLEASE SEE ALL
 INFORMATION REQ'D ON TITLE BLOCKS FOR
 PLANS. REQ'D ALSO UNDER FS 471/481
  
 PLEASE NOTE; PLANS HAVE ONLY COME IN FOR
 PLAN REVIEW AND NOT FOR PERMIT.
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  