| Plan Review Notes For Permit 03080042 |
| Permit Number |
03080042 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-20 00:00:00 | ************ UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL | | | EM.EXT LTS PER 700.12E. | | | | | | 2)NOTE: PLEASE SUBMIT FIXTURE SCHEDULES | | | CONTAINING WATTAGES/VOLTAGES FOR FIXTURE | | | -S. | | | | | | 3)NOTE: PLEASE CORRELATE CIRCUITING ON | | | PLANS WITH SUBMITTED PANEL SCHEDULES/ | | | MAX LOAD PER CIRCUIT. | | | A COMPLETE AND ACCURATE PANEL SCHEDULES | | | WILL BE REQ'D BEFORE FINAL ALSO. | | | | | | 4)NOTE: PLEASE INCLUDE LOADS ON PANELS | | | 215.5 | | | | | | | | | 5)NOTE: PLEASE SEE ATTACHED COPIES OF | | | FAC 61G15-23.002 FOR ENGINEERS AND | | | 61G1-16.004 FOR ARCH'S. PLEASE SEE ALL | | | INFORMATION REQ'D ON TITLE BLOCKS FOR | | | PLANS. REQ'D ALSO UNDER FS 471/481 | | | | | | PLEASE NOTE; PLANS HAVE ONLY COME IN FOR | | | PLAN REVIEW AND NOT FOR PERMIT. | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | REVIEWS THAT MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|