| 2004-09-23 00:00:00 | ********* UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SEE ORIGIANL PLANS ARE |
| | SIGNED AND SEALED BY AN ENGINEER. |
| | ANY REVISIONS TO PLANS ON FILE MUST BE |
| | REVISED ORIG ENG. |
| | FS 471 |
| | PLEASE CALL FOR OTHER OPTIONS. |
| | |
| | 2)NOTE: PLEASE SEE THERE ARE NUMEROUS |
| | CIRCUITS SHOWN ON PANEL SCHEDULES WHICH |
| | SHOW 20A BRKR AND #14 AWG. |
| | PLEASE SEE MANY OF THESE CIRCUITS ARE |
| | REQUIRED TO BE 20A CIRCUITS. |
| | |
| | 3)NOTE: PLEASE SEE ALL EQUIPMENT LISTED |
| | ON PANEL "D" ARE NOT SHOWN ON PLAN? |
| | PLEASE ALSO SEE WATER HEATER INDICATED |
| | IN SHED BUT NOT ON PANLE SCHEDULE? |
| | |
| | 4)NOTE: PLEASE SEE A WATER HEATER IS |
| | SHOWN ON PANEL "B" BUT NOT SHOWN ON MAIN |
| | HOUSE PLANS? |
| | |
| | 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED. 210.8A6 |
| | |
| | 6)NOTE: PLEASE SEE 210.52C1-5 FOR REQ'D |
| | RECEPT SPACING ALONG KITCHEN COUNTER- |
| | -SPACE. THERE ARE SOME MISSING. |
| | |
| | 7)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANEL "A" FOR SUB-FEED CONDCUTOR |
| | SIZES. |
| | |
| | 8)NOTE: PLEASE SEE OCP AND AWG FOR BOTH |
| | AHU'S. SHOWS 50A OCP AND #6 FOR 5KW |
| | HEAT INDICATED ON LOAD CALCULATIONS?? |
| | 424.3B |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |