Plan Review Notes
Plan Review Notes For Permit 03080040
Permit Number 03080040
Review Stop B
Sequence Number 3
Notes
Date Text
2004-02-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.) TWO COPIES OF ALL PERMIT DOCUMENTS
 MUST BE SUBMITTED.ONLY ONE COPY OF THE
 HVAC CALCS, RAILING DETAIL, AND SURVEY
 WAS SUBMITTED.
  
 2.)SEPARATE PERMIT REQUIRED FOR
 FENCING; PRODUCT APPROVALS NOT
 REQUIRED.
  
 3.)STUCCO OVER WIRE LATH IN A VERTICAL
 APPLICATION IS TO BE 7/8", FBC2504.2.2,
 ASTM C926.
  
 4.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 5.)GUARDRAILS ARE TO COMPLY WITH
 FBC1608.2.2 AND FBC1007.SUBMIT A
 DETAIL SHOWING COMPLIANCE BEFORE
 INSTALLATION.
  
 6.)THE PRINTED LICENSE NUMBER OF
 THE PERSON SEALING THE PLAN IS TO BE
 ON EACH SHEET, FAC61G15-23.002.
  
 7.)CONNECTOR CS185 (SHEET A5) IS NOT
 IN THE SIMPSON CATALOG.CS18 FASTENING
 CONFLICTS WITH THE CATALOG.ALL
 CONNECTORS SPECIFIED SHOULD BE FROM
 THE HIGH WIND CATALOG.FASTENING WHICH
 IS NOT CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS ARE TO
 EITHER HAVE A TECHNICAL BULLETIN
 SUPPLIED BY THE MANUFACTURER OR
 SEALED ENGINEER'S CALCULATIONS.CHECK
 ALL CONNECTORS.
  
 8.)PROVIDE THE APPROVED SITE PLAN
 STAMPED BY ZONING.
  
 9.)TRUSS BOTTOM CHORD LIVE LOAD IS TO
 BE A MINIMUM OF 10, FBC TABLE 16014.1.
 THE ENGINEER'S TITLE BLOCK IS TO BE ON
 EVERY SHEET.A PHOTOCOPY OF A SIGNATURE
 IS NOT ACCEPTABLE.CORRECTED TRUSS
 DRAWINGS MUST BE AVAILABLE AT TIME OF
 INSPECTION.
  
 10.)SUBMIT THE ORIGINAL APPROVED
 MECH/ELEC/PLUMBING SHEETS.THE SHEETS
 SUBMITTED WERE PHOTOCOPIES; MUST BE
 SIGNED/SEALED WHEN AN ENGINEER'S TITLE
 BLOCK IS ON THE PAGE.
  
 11.)WHEN RESUBMITTING, REMOVE OLD
 SHEETS AND REPLACE WITH REVISED SHEETS.
 SUBMIT OLD SHEETS SEPARATELY.