| 2004-02-23 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.) TWO COPIES OF ALL PERMIT DOCUMENTS |
| | MUST BE SUBMITTED.ONLY ONE COPY OF THE |
| | HVAC CALCS, RAILING DETAIL, AND SURVEY |
| | WAS SUBMITTED. |
| | |
| | 2.)SEPARATE PERMIT REQUIRED FOR |
| | FENCING; PRODUCT APPROVALS NOT |
| | REQUIRED. |
| | |
| | 3.)STUCCO OVER WIRE LATH IN A VERTICAL |
| | APPLICATION IS TO BE 7/8", FBC2504.2.2, |
| | ASTM C926. |
| | |
| | 4.)ENERGY CALCS REQUIRED FBC13-101.2. |
| | |
| | 5.)GUARDRAILS ARE TO COMPLY WITH |
| | FBC1608.2.2 AND FBC1007.SUBMIT A |
| | DETAIL SHOWING COMPLIANCE BEFORE |
| | INSTALLATION. |
| | |
| | 6.)THE PRINTED LICENSE NUMBER OF |
| | THE PERSON SEALING THE PLAN IS TO BE |
| | ON EACH SHEET, FAC61G15-23.002. |
| | |
| | 7.)CONNECTOR CS185 (SHEET A5) IS NOT |
| | IN THE SIMPSON CATALOG.CS18 FASTENING |
| | CONFLICTS WITH THE CATALOG.ALL |
| | CONNECTORS SPECIFIED SHOULD BE FROM |
| | THE HIGH WIND CATALOG.FASTENING WHICH |
| | IS NOT CONSISTENT WITH THE |
| | MANUFACTURER'S SPECIFICATIONS ARE TO |
| | EITHER HAVE A TECHNICAL BULLETIN |
| | SUPPLIED BY THE MANUFACTURER OR |
| | SEALED ENGINEER'S CALCULATIONS.CHECK |
| | ALL CONNECTORS. |
| | |
| | 8.)PROVIDE THE APPROVED SITE PLAN |
| | STAMPED BY ZONING. |
| | |
| | 9.)TRUSS BOTTOM CHORD LIVE LOAD IS TO |
| | BE A MINIMUM OF 10, FBC TABLE 16014.1. |
| | THE ENGINEER'S TITLE BLOCK IS TO BE ON |
| | EVERY SHEET.A PHOTOCOPY OF A SIGNATURE |
| | IS NOT ACCEPTABLE.CORRECTED TRUSS |
| | DRAWINGS MUST BE AVAILABLE AT TIME OF |
| | INSPECTION. |
| | |
| | 10.)SUBMIT THE ORIGINAL APPROVED |
| | MECH/ELEC/PLUMBING SHEETS.THE SHEETS |
| | SUBMITTED WERE PHOTOCOPIES; MUST BE |
| | SIGNED/SEALED WHEN AN ENGINEER'S TITLE |
| | BLOCK IS ON THE PAGE. |
| | |
| | 11.)WHEN RESUBMITTING, REMOVE OLD |
| | SHEETS AND REPLACE WITH REVISED SHEETS. |
| | SUBMIT OLD SHEETS SEPARATELY. |