2003-11-03 00:00:00THE SURVEY DOES NOT AGREE WITH THE SITE
 PLAN ON THE SOUTH ELEVATION.
  
 SHEET A2 DOES NOT HAVE INFORMATION FOR
 THE 2-2X6 TO SUPPORT THE H-7 TRUSS LIKE
 GRADE, SPECIES, LAP LENGHT OR FASTENING
 METHODS.
  
 THE NEW 24"X24" FOOTING DOES NOT A
 LENGTH MEASUREMENT, MINIMUM SOIL
 BEARING VALUE OR DEPTH BELOW GRADE.
  
 WHAT WILL BE DOWELED TO THE EXISTING
 FOOTER BETWEEN THE DINING ROOM AND
 KITCHEN.
  
 THE ROOM DIMENSIONS DO NOT DEFINE THE
 NEW CONSTRUCTION TO THE EXISTING.
  
 THE 18'X5' PORCH DOES NOT HAVE
 DIMENSIONS TO LOCATE THE FOOTING PIERS.
  
 THERE ARE NO DETAILS FOR THE
 CONSTRUCTION OF THE BREAKFAST ROOM WALL
 @ THE 45 DEEGREE ANGLE.
  
 THE TYPICAL HEADER DETAIL DOES NOT SHOW
 A CONTINUOUS LOAD PATH TO THE
 FOUNDATION.
  
 THERE ARE NO FRAMING PLANS FOR THE
 SECOND FLOOR.
  
 THE DELEGATION OF TRUSS DESIGN IS NOT
 SHOWN OR LOADS SPECIFIED.
  
 THERE IS STILLNO INFORMATION FOR THE
 CONNECTION OF THE TRUSSES TO THE
 EXISTING ROOF OR THE REQUESTED
 COMPUTATIONS TO DEMONSTRATE THE
 CAPABILITY OF THE EXITING CONSTRUCTION.
 TAX RECORDS INDICATE THIS HOUSE WAS
 CONSTRUCTED PRIOR TO 1940.
  
 IN SECTION CC, WHAT WILL THE HEAD ROOM
 BE ON THE SECOND FLOOR BALCONY?