| Plan Review Notes For Permit 03080040 |
| Permit Number |
03080040 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT P-1 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS, NOR DOES IT | | | REFLECT THE FLOOR PLAN. | | | A) ONLY THE FIXTURES WITHIN THE BATH- | | | ROOM GROUPS SHALL CONNECT TO THE WET- | | | VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. SEC 909.1 | | | WASH MACHINE ON 2ND FLOOR. | | | B) STANDPIPES ARE REQUIRED AT WASH | | | MACHINES. | | | C) SHOWER BATHROOM 2ND FLOOR SHOWS TWO | | | LAVS ON FLOOR PLAN, BUT ONLY ONE ON SANT | | | RISER DIAGRAM. | | | 2) SHOW DIMENSIONS FOR SHOWERS. MINIMUM | | | SIZE 900 SQ INCHES. SHOWER COMPARTMENTS | | | SHALL NOT BE LESS THAN 30" INSIDE FIN- | | | ISHED SIDE TO SIDE. SECTION 417.4. | | | 3) SHOW SIZE OF OPENINGS FOR ALL WATER | | | CLOSETS. PER SECTION 504.3.1 | | | 4) SHOW MEASUREMENTS FOR TOILET ROOMS | | | 5) PROVIDE DETAILS FOR FLOOR DRAINS. IN- | | | DICATE HOW THESE WILL BE MADE WATERPROOF | | | OR WATER TIGHT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|