Plan Review Notes
Plan Review Notes For Permit 03080040
Permit Number 03080040
Review Stop P
Sequence Number 1
Notes
Date Text
2003-08-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUPS SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SEC 909.1
 WASH MACHINE ON 2ND FLOOR.
 B) STANDPIPES ARE REQUIRED AT WASH
 MACHINES.
 C) SHOWER BATHROOM 2ND FLOOR SHOWS TWO
 LAVS ON FLOOR PLAN, BUT ONLY ONE ON SANT
 RISER DIAGRAM.
 2) SHOW DIMENSIONS FOR SHOWERS. MINIMUM
 SIZE 900 SQ INCHES. SHOWER COMPARTMENTS
 SHALL NOT BE LESS THAN 30" INSIDE FIN-
 ISHED SIDE TO SIDE. SECTION 417.4.
 3) SHOW SIZE OF OPENINGS FOR ALL WATER
 CLOSETS. PER SECTION 504.3.1
 4) SHOW MEASUREMENTS FOR TOILET ROOMS
 5) PROVIDE DETAILS FOR FLOOR DRAINS. IN-
 DICATE HOW THESE WILL BE MADE WATERPROOF
 OR WATER TIGHT.
  