2003-08-18 00:00:00PROVISO
 FAILED
 ~~~~~~
 PLEASE MAKE NECESSARY CHANGES TO PLANS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PANEL "B" MUST BE GROUNDED PER
 250-32,PLEASE SHOW SAME ON PLANS.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 3} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210.12
  
 6} THE DINING ROOM RECEPTACLE SPACING
 MUST COMPLY WITH 210.52(A)(1).
  
 7} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST BE GFI PROTECTED PER 210.8(A)(6).
 AND THE SPACING PER210.52(C)(1).
  
 8} THE BEDROOMS NEED RECEPTACLES ADDED
 TO COMPLY WITH 210.52(A)(1)&(2).
  
 9} THE BEDROOMS MUST COMPLY WITH 210.70.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.