| 2003-08-18 00:00:00 | PROVISO |
| | FAILED |
| | ~~~~~~ |
| | PLEASE MAKE NECESSARY CHANGES TO PLANS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PANEL "B" MUST BE GROUNDED PER |
| | 250-32,PLEASE SHOW SAME ON PLANS. |
| | |
| | 2} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110.9. |
| | |
| | 3} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210.52E. |
| | |
| | 4} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210.12 |
| | |
| | 6} THE DINING ROOM RECEPTACLE SPACING |
| | MUST COMPLY WITH 210.52(A)(1). |
| | |
| | 7} THE KITCHEN COUNTERTOP RECEPTACLES |
| | MUST BE GFI PROTECTED PER 210.8(A)(6). |
| | AND THE SPACING PER210.52(C)(1). |
| | |
| | 8} THE BEDROOMS NEED RECEPTACLES ADDED |
| | TO COMPLY WITH 210.52(A)(1)&(2). |
| | |
| | 9} THE BEDROOMS MUST COMPLY WITH 210.70. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |