Plan Review Notes
Plan Review Notes For Permit 03080040
Permit Number 03080040
Review Stop B
Sequence Number 1
Notes
Date Text
2003-09-09 00:00:00PLEASE PROVIDE A RECENT SIGNED, SEALED
 AND DATED PROPERTY SURVEY.
  
 THE SITE PLAN ON SHEET A1 IS NOT CLEAR
 AS TO THE SIZE AND LOCATION OF THE
 ADDITION AND PORCHES.THE OTHER SHEETS
 ARE LACKING DIMENSIONS AS WELL FOR THE
 NEW WORK.PLEASE REVISE AS NECESSARY.
  
 THE DRIVE APPROACH SHOWN ON SHEET A1 IS
 NOT ACCEPTABLE IN WEST PALM BEACH.
 CONTACT M. AMINI AT 805-6723 FOR
 SPECIFIC INFORMATION.
  
 THE ROOF TRUSSES DATED 7/29/03 DO NOT
 SHOW THE MINIMUM 10# LIVE LOAD FOR THE
 BOTTOM CHORD IN ACCORDANCE WITH FBC
 TABLE 1604.1 FOR ATTICS WITHOUT STORAGE.
 PLEASE REVISE AS NECESSARY.
  
 THE TRUSS ENGINEERING SHOWS A 15# DEAD
 LOAD FOR THE TOP CHORD.SINCE A
 CONCRETETILE ROOF COVERING IS PROPOSED,
 WHAT IS THE ASSUMED WEIGHT OF
 MATERIALS?IE; PLYWOOD SHEATHING, FELT
 MATERIALS, ETC.HAS THE ENGINEER OF
 RECORD REVIEWED THE TRUSS DRAWINGS?
  
 SEVERAL OF THE TRUSSES ARE SHOWN AS
 SUPERIMPOSING POINT LOADS > 1000 LBS ON
 THE EXISTING ROOF STRUCTURE AS WELL AS
 INTERIOR BEARING WALLS NOT INDICATED ON
 THE PLANS.
 PLEASE PROVIDE COMPUTATIONS
 DEMONSTRATING THE ABILITLY OF THE
 EXISTING STRUCTURE
 TO SUPPORT THE NEW CONSTRUCTION.
  
 SHEET A3.PROVIDE A FRAMING DETAIL FOR
 THE TWO NEW DOOR OPENINGS ON THE FRONT
 PORCH SECOND FLOOR BALCONY.FBC 104.2.
  
 WHAT IS THE DESIGN LOAD FOR THE BALCONY?
  
 PLEASE SHOW A CONSTRUCTION DETAIL AND
 DESIGN LOADS FOR THE BALCONY GUARD
 RAILS. SEE FBC 104.2.
  
 WHAT IS THE SPACING OF THE FRONT PORCH
 COLUMNS?
  
 SHEET A3, SECTION C-C. THE NOTE "2X6
 STRAPPED TO EXISTING WALL STUDS" IS
 POOR ENGINEERING DESIGN FOR A BALCONY.
 PLEASE PROVIDE A CONSTRUCTION DETAIL
 WITH SPECIFIC INFORMATION.
  
 SECTION A-A CALLS OUT J BOLTS FOR
 ANCHORING THE BOTTOM PLATE.WILL THERE
 BE ANY WASHERS?
  
 THE FRONT AND REAR PORCHES INDICATE
 STEPS.PLEASE PROVIDE DIMENSIONS AND
 CONSTRUCTION DETAILS.
  
 A3 SECTION C-C.THE ROOF CONNECTION FOR
 THE PORCH TO THE EXISTING.WILL THERE
 BE ANY MODIFICATION TO THE EXISTING FOR
 UPLIFT?
  
 SHEET A2. WHAT IS THE SPACING OF THE
 RAFTERS, SHEATHING AND DESIGN LOAD FOR
 THE SHED ROOF?SEE FBC 104.2.
  
 WHAT IS THE FOOTING SIZE FOR THE SHED?
  
 SHOW THE TERMITE TREATMENT FOR THE SOIL
 AS PROVIDED FOR IN FBC 1816.
  
 SHEET A2.WHAT IS THE NOTE IN THE
 DINING ROOM AREA "DOWEL INTO EXISTING
 FOOTING" INDICATIVE OF?
  
 SHOW THE ATTIC ACCESS AND VENTILATION AS
 REQUIRED BY FBC 2309.6 AND 2309.7.
  
 THE ADDITION MAY BE SUBJECT TO IMPACT
 FEES COLLECTED BY COUNTY.THE PERMIT
 PLANS MUST BE STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION BEFORE A
 PERMIT MAY BE ISSUED.CALL
 561-233-5025 FOR MORE INFORMATION.