| 2003-08-25 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - HORIZONTAL SLIDING WINDOWS |
| | |
| | 4) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | U.L.LISTING INFORMATION FOR THE ONE HOUR |
| | FIRE RATED GLASS BLOCK. |
| | |
| | 5) REVISE STUCCO NOTES ON A6. HIGH RIB |
| | METAL LATH IS REQUIRED TO BE FASTENED AT |
| | EACH RIB (4"OC) PER ASTM C 1063. SEE |
| | FBC 2504.2.2. |
| | |
| | 6) SUBMIT A LINTEL SCHEDULE. |
| | |
| | 7) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. SPECIFY THE |
| | MOUNTING TYPE AND CONNECTION TYPE. |
| | |
| | 8) REVISE THE BUCK DETAIL ON A8. THE |
| | FRAMES ARE REQUIRED TO BE FASTENED |
| | THROUGH THE 1X BUCKS INTO THE SUBSTRATE |
| | PER FBC 1707.4.4.2. |
| | |
| | 9) THE FBC 11-4.23.2 REQUIRES AT LEAST |
| | ONE BATH ROOM WITH A DOOR THAT HAS A 29 |
| | INCH CLEAR OPENING. IF A FULL BATH IS |
| | PROVIDED AT GRADE LEVEL, IT IS REQUIRED |
| | TO COMPLY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |