| Plan Review Notes For Permit 03072358 |
| Permit Number |
03072358 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-03 00:00:00 | ************ PROVISO/REVISION ******** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. | | | PLEASE SEE 700.12E FOR CIRCUITING OF | | | EM/EXT LTS. | | | | | | PLEASE SEE THAT A SEPARATE ELECTRICAL | | | PERMIT IS REQ'D. THIS WORK WAS NOT UNDER | | | PREVIOUS ELECTRICAL PERMIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE FINAL ELECTRICAL INSPECT- | | | -ION | | | PLEASE ALSO SUBMIT ANY OTHER REVISIONS. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|