| Plan Review Notes For Permit 03072358 |
| Permit Number |
03072358 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-01 00:00:00 | ******************* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF | | | FAC 61G1-16.004 FOR REQ'D MISSING | | | INFORMATION FOR ARCH'S TITLE BLOCK. | | | FS 481 | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. | | | PLEASEPROVIDE LOAD CALC ON PANEL FOR | | | ADDING OF NEW CIRCUITS AND A/C SYSTEM | | | | | | 3)NOTE: PLEASE SHOW LOCATION OF NEW | | | A/C SYSTEM AND REQ'D DISC'S 440.11 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|