| Plan Review Notes For Permit 03072274 |
| Permit Number |
03072274 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 BLDG. | | | FLORIDA STATUTES | | | WPB CITY CODE | | | | | | 1) FOLLOWING COMMENTS FROM PREVIOUS RE- | | | VIEW NOT ADDRESSED. COMMENT NUMBER TO | | | BE THE SAME FOR CLAIRITY. | | | 2) MANUFACTURE INFORMATION REQUIRED FOR | | | WATER FILTERS. NSF APPROVAL REQUIRED. | | | SUBMIT SPECIFICATION SHEETS. | | | 7) WATER HAMMER ARRESTORS SHALL BE LOCA- | | | TED NEAR THE FIXTURE NOT IN THE CEILING | | | AS SHOWN. PDI-WH 201 & MANUF. INSTALL. | | | INSTRUCTIONS. | | | 10) SHT C-3 WATER, WASTEWATER, UTILITIES | | | NOTE #2 INDICATES AN IRRIGATION WELL, | | | BUT SHTS L-2 & L-3 INDICATES A METER & | | | BACKFLOW. PLEASE CLAIRFY. | | | 14) SPECIFICATION WORK SHEETS FROM DBPR | | | ARE REQUIRED ON EACH SET OF PLANS. WHEN | | | REVIEWED, MORE COMMENTS MAY BE ADDED. | | | SUBMIT WORK SHEETS AT RESUB TO THE CITY | | | OF WPB FOR REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|