Plan Review Notes
Plan Review Notes For Permit 03072274
Permit Number 03072274
Review Stop P
Sequence Number 1
Notes
Date Text
2003-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BLDG.
 FLORIDA STATUTES
 CITY CODE
  
 1) SHT P-1 CONTACT RODNEY COMPO ENVIRON-
 MENTAL COMPLIANCE, FOR SIZING THE GREASE
 INTERCEPTOR. CITY WASTE ORD. #2938-96.
 (561) 837-4074. OR IN HIS ABSENCE CALL
 MARI ORTIZ (561) 837-4061.
 2) SHT P-1 WATER FILTERS SHALL BE "NSF"
 COMPLIANT. MANUFACTURE INFO REQUIRED.
 SUBMIT SPEC. SHEETS.
 3) SHT P-1 & SHT P-2 FD1 BY MAIN ENTRAN-
 CE STATES 15' MAX. FROM VENT. TABLE NO.
 906.1 SHOWS MAX. 10' FROM VENT.
 4) SHT P-1 FLOOR DRAIN IN DUMPSTER PAD.
 INFORMATION REQUIRED AS TO HOW THE RAIN
 WILL BE KEPT OUT OF GREASE LINE. IF UN-
 ABLE TO KEEP RAIN OUT, THE DRAIN FOR THE
 DUMPSTER PAD WILL NOT BE APPROVED.
 5) SHTS P-1 & P-2 FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE INTERCEPTORS. A
 FLOOR SINK OR HUB DRAIN SHALL BE REQUIR-
 ED. SECTIONS 802.1, 802.3, & 802.3.2.
 FLOOR SINKS & HUB DRAIN SHALL BE LOCATED
 SO AS NOT TO BE A TRIPPING HAZARD UNDER
 TABLES OR FIXTURES.
 6) SHT P-2 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED. SECTION
 607.3.2
 7) SHT P-3 WATER SUPPLY ISOMETRIC, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 ISOMETRIC. SECTION 604.9 WATER HAMMER
 ARRESTORS REQUIRED AT QUICK CLOSING
 VALVES, (ICE MAKERS, DISHWASHERS ECT),
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF THE
 DROPS IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 8) SEPARATE PERMITS REQUIRED FOR GREASE
 TRAP AND IRRIGATION.
 9) ALL SHEETS SEE ATTACHED SHEETS CON-
 CERNING TITLE BLOCKS. 61G15-23.002(2)
 SEE HIGHLIGHTED SECTION.
 10) SHT C-3 WATER, WASTEWATER, UTILITIES
 NOTE #2 INDICATES A IRRIGATION WELL, BUT
 SHTS L-2 & L-3 INTICATES A METER & BACK-
 FLOW. PLEASE CLAIRFY.
 11) SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 HDCP FIXTURES AND TURNING SPACE PER SEC
 11-4.22.3
 12) SHT A-3 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE OF ROOF, AND ADD 1/2 AREA
 OF ALL VERTICAL WALLS IN CALCULATIONS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 13) SHT A-3 ONLY OVERFLOW SCUPPER SHOWN
 ON ROOF PLAN. SECTION 1503.4.2 STATES
 THAT OVERFLOW SCUPPERS SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTI-
 CAL LEADERS OR DOWNSPOUTS. (SEE ATTACHED
 SHEET). PLEASE CLAIRFY. - IF ONLY OVER-
 FLOW SCUPPER IS USED MINIMUM SIZE SHALL
 BE 5"X16" - 76"SQ IN REQUIRED.
 14) SPECIFICATION WORK SHEETS FROM DBPR
 ARE REQUIRED ON EACH SET OF PLANS. WHEN
 REVIEW MORE COMMENTS MAY BE ADDED. SUB-
 MIT WORK SHEETS AT NEXT RESUB TO THE
 CITY WPB FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]