Plan Review Notes
Plan Review Notes For Permit 03072274
Permit Number 03072274
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) INFORMATIVE:
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) INFORMATIVE:
 IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC* 104.1.1A SEPARATE PERMIT
 APPLICATION WILL BE REQUIRED FOR THE
 AWNINGS.
  
 4) TITLE SHEET, GENERAL NOTE 4 REFERS TO
 SOUTH FLORIDA BUILDING CODE.THE
 APPLICABLE CODE IS FLORIDA BUILDING
 CODE.AMEND THE NOTE.
  
 5) FBC 11-4.6.3PARKING ACCESS AISLE.
 SHEETS SP-B, C1, C2, C3, SG1, L1 AND L2
 ALL SHOW THE EAST ACCESSIBLE PARKING
 SPACE WITHOUT THE REQUIRED PARKING
 ACCESS AISLE.AMEND THE PLANS TO SHOW A
 5' MIN. ACCESS AISLE ADJACENT TO THE
 PARKING SPACE.
  
 6) FBC 1511.7SHEET A-3ROOF PLAN AND
 DETAILS.ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS 8" MIN. ABOVE
 THE ROOF SURFACE OR, WHERE THE ROOFING
 EXTENDS BENEATH THE UNIT, ON RAISED
 EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 HEIGHT CLEARANCE IN ACCORDANCE WITH
 TABLE 1511.7
  
 7) FBC 1606.1.1TITLE SHEET, GENERAL
 NOTE 5 AND SHEETS S-2 & S-3 STATE A
 BASIC WIND SPEED OF 130 MPH.THE CITY
 OF WEST PALM BEACH IS WITHIN THE 140 MPH
 REGION.AMEND THE WIND SPEED AND
 RECALCULATE THE DESIGN PRESSURES ON
 SHEETS S-2 AND A-2 ACCORDINGLY.
  
 8) FBC 1606.1.7WIND LOAD.IN ADDITION
 TO THE WIND SPEED AND EXPOSURE CATEGORY,
 THE PLANS SHALL STATE THE IMPORTANCE
 FACTOR, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.ANNOTATE THE
 PLANS.
  
 9) FBC 1606.1.1SHEET A-2. THE WEST AND
 NORTH ELEVATIONS, SHOWING THE WALK-IN
 COOLER, MAKE REFERENCE TO ASCE 7-88 AND
 110 MPH (FASTEST MILE?) WIND SPEED.THE
 CURRENT REFERENCE IS ASCE 7-98 AND THE
 CORRECT WIND SPEED (3 SEC. GUST) IS
 140 MPH.AMEND THE PLAN.ALSO, THE
 STATED MIAMI-DADE PRODUCT APPROVAL
 NOA# 99-0426.05 EXPIRED ON 8/22/02.IT
 IS NOTED THAT THE SUBMITTED PRODUCT
 APPPROVAL NOA# 02-0625.04 RENEWS THE
 EXPIRED ONE.
  
 10) FBC 1606.2.4SHEET S-2, ROOF
 FRAMING PLAN.THE UPLIFT CAPACITY OF
 TRUSS ANCHOR MARK 1, FROM THE TRUSS TIE-
 DOWN SCHEDULE, IS STATED AS 1410 LBS.
 NUMEROUS LOCATIONS ON THE ROOF FRAMING
 PLAN CALL UP TRUSS ANCHOR MARK 1
 EVENTHOUGH THE CALCULATED UPLIFT FOR
 THOSE LOCATIONS EXCEEDS 1410 LBS (VARIES
 UPTO 1644 LBS).
  
 11) FBC 1606.2.4SHEET S-2.THE TRUSS
 TIE-DOWN SCHEDULE STATES THAT ANCHOR
 MARK 3 (USP TAPL16) WILL BE CONNECTED TO
 THE TRUSS USING (11) 10DX1-1/2" NAILS
 WHICH IS LESS THAN THE (13) 10D NAILS
 REQUIRED BY THE 2003 USP CATALOGUE TO
 GIVE THE STATED CAPACITY.AMEND THE
 SCHEDULE.
  
 12) FBC 1606.2.4SHEET S-2, TRUSS TIE-
 DOWN SCHEDULE.IT IS NOTED THAT THE
 STATED 1410 LBS UPLIFT CAPACITY FOR
 ANCHOR MARK 1 (USP DTC) IS TAKEN FROM
 MIAMI-DADE PCNA# 01.0724.06.THE STATED
 UPLIFT CAPACITY EXCEEDS THE CAPACITY
 GIVEN IN THE 2003 (AND PREVIOUS) USP
 CATALOGUE.
  
 13) 'HUGHES' CONNECTORS.DETAILS 2/S-2,
 5/S-3, 6/S-3 AND 7/S-3 ALL SPECIFY
 ANCHORS BY 'HUGHES' WHO NO LONGER SUPPLY
 ANCHORS.AMEND THE DETAILS.
  
 14) INFORMATIVE:
 SHEET A-4, SECTION A REFERS TO 'BROWARD
 COUNTY APPROVED STORM SHUTTER'.THE
 SHUTTERS SHALL HAVE MIAMI-DADE PRODUCT
 APPROVAL, ICC-ES (SBCCI) EVALUATION
 REPORT OR SITE-SPECIFIC ENGINEERING.
 SEE COMMENT 15 BELOW.
  
 15) THE GALVANIZED STEEL STORM PANEL
 PRODUCT APPROVAL NOA# 00-0726.06 EXPIRES
 8/22/03. AS EXPIRATION WILL OCCUR BEFORE
 A PERMIT APPLICATION IS LODGED, AN
 ALTERNATIVE PRODUCT APPROVAL WILL BE
 REQUIRED.
  
 16) FBC 1707.4.2SHEET A-2, SOUTH ELEV.
 DRAWING SHEET 1 OF THE SUBMITTED ALUM.
 SLIDING PASS THROUGH WINDOW PRODUCT
 APPROVAL NOA# 02.0806.02 STATES DESIGN
 PRESSURE RATINGS OF +43.3 AND -46.0
 WHICH ARE LESS THAN THE DESIGN WIND
 PRESSURES STATED ON THE ELEVATION.
 SUBMIT AN ALTERNATIVE PRODUCT APPROVAL.
  
 17) FBC 1707.4.2DRAWING SHEET 5 OF THE
 SUBMITTED OUTSWING ALUMINUM DOOR PRODUCT
 APPROVAL NOA# 01-0226.05 IS A POOR COPY
 AND CANNOT BE READ.SUBMIT TWO LEGIBLE
 COPIES.
  
 18) FBC 1606.3DRAWING SHEETS 5 AND 6
 OF THE SUBMITTED SINGLE PLY PVC ROOF
 SYSTEM PRODUCT APPROVAL NOA# 02-0710.04
 REFER TO 'GENERAL LIMITATION #7' FOR
 ENHANCED UPLIFT PRESSURE (IN EXCESS OF
 -45 PSF) REQUIREMENTS.THIS WILL APPLY
 TO THE EDGE AND CORNER ZONE PRESSURES
 (ZONES 2 & 3).THE PLANS, OR ANNOTATION
 ON THE THE PRODUCT APPROVAL, SHALL SHOW
 THE RELEVANT MAXIMUM COMPONENT AND
 CLADDING PRESSURE FOR THE ROOF COVERING
 AND STATE THE ENHANCED FASTENER AND TAB
 SPACING TO RESIST THAT PRESSURE IN
 ACCORDANCE WITH ROOFING APPLICATION
 STANDARD RAS117.
  
 19) SHEET SP-2, SPECIFICATION DIVISION 3
 CONCRETE, 'SLAB AND FOOTINGS' REFERS TO
 3000 PSF REINFORCED CONCRETE, AND
 'SIDEWALKS AND RAMPS' REFERS TO 3500 PSF
 AIR ENTRAINED CONCRETE. SHOULD THE 'PSF'
 READ 'PSI'?
  
 20) FBC 3502SHEET SP-3, SPECIFICATION
 DIVISION 9 - FINISHES, A: GENERAL,
 ITEM 3 (QUALITY ASSURANCE) AND
 B: PRODUCTS, ITEM 1 (MATERIALS) 'G' BOTH
 REFER TO ASTM C 1063-86. THE CODE REFERS
 TO ASTM C 1063-99.
  
 21) 61G15-23.002 FL ADMINISTRATIVE CODE
 PLANS SIGNED AND SEALED BY AN ENGINEER
 SHALL HAVE EITHER THE NAME, ADDRESS AND
 LICENSE NUMBER OF THE ENGINEER, OR THE
 CERTIFICATE OF AUTHORIZATION NUMBER OF
 THE ENGINEERING BUSINESS, PRINTED ON
 EACH SHEET.
  
 22) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS