| Plan Review Notes For Permit 03072203 |
| Permit Number |
03072203 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-08 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR ADDING ADDITIONAL LOADS OF NEW | | | WASHER AND DRYER.PLEASE SHOW SIZE OF | | | EXISTING PANEL. 215-5 | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210-52 | | | | | | 3)NOTE: PLEASE SHOW THE REQ'D ARC-FAULT | | | PROTECTED CIRCUITS PER 210-12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|